Section 7: Resource Block
January 2022
19
20
Table 26.
Enumeration
0
1
2
3
4
21
22
Table 27.
Enumeration
0
1
44
SAFETY_POSITION
Type: FLOAT
Size: 4 octets
Handling: READ and STATIC WRITE
Range: 0.0 – 100.0
Unit: %
It is the position to drive the actuator when the SAFETY_BEHAVIOUR is programmed to
'Go to position' (= 4).
ESD_ACTION
Type: ENUMERATED
Size: 1 octet
Handling: READ and STATIC WRITE
This parameter defined the action to run in case of an ESD command. The possible actions are
the following:
ESD_POSITION
Type: FLOAT
Size: 4 octets
Handling: READ and STATIC WRITE
Range: 0.0 – 100.0
Unit: %
It is the position to drive the actuator when the ESD_ACTION is programmed to
'Go to position' (= 4).
DO_INTERLOCK_TABLE
Type: ENUMERATED
Size: 1 octet
Handling: READ and STATIC WRITE
Default value: 0
This parameter is a legacy from previous version of this interface.
The changing of this parameter does not have effect. In this version. The DO Interlock table
must be carefully checked by host programmer to avoid unexpected stroke of actuator.
The possible actions are the following:
Installation, Operation and Maintenance Manual
Description
Off: function disabled
Close
Open
Stayput
Go to position
Description
Disabled
Enabled
MDE 255 Rev. 0
Resource Block