Installation, Operation and Maintenance Manual
MDE 255 Rev. 0
15
16
17
Table 25.
Enumeration
0
1
2
3
4
18
Resource Block
DEAD_BAND
Type: FLOAT
Size: 4 octets
Handling: READ and STATIC WRITE
Range: 0.1 – 25.5
Unit: %
The Dead band is configurable from 0.1% to 25.5%. The configured value should be great enough
to avoid "hunting" effect of the actuator.
POS_MOT_IN_TIMER
Type: UNSIGNED8
Size: 1 octet
Handling: READ and STATIC WRITE
Range: 0 – 255
Unit: second
Motion inhibit time: it allows to adjust the length of the delay time between two cycles of the
motor. It can be configured from 0 to 255 seconds and allows to set the maximum number of
start per hour of the electrical motor.
SAFETY_BEHAVIOUR
Type: ENUMERATED
Size: 1 octet
Handling: READ and STATIC WRITE
This parameter defined the action to run in case of loss of communication with the fieldbus
interface card or if an output FB is set to OOS or has been removed from the FB schedule.
The possible actions are the following:
DELAY_SAFE_OPERATION
Type: UNSIGNED8
Size: 1 octet
Handling: READ and STATIC WRITE
Range: 0 – 255
Unit: second
This parameter is configured from 0 to 255 seconds and defines the delay before run the safety
behaviour programmed in SAFETY_BEHAVIOUR.
Section 7: Resource Block
Description
Off: function disabled
Close
Open
Stayput
Go to position
January 2022