Section 7: Resource Block
January 2022
Value
0x00400000 Extremely high torque in opening
0x00200000 Extremely high torque in closing
0x00100000 Jammed valve in opening
0x00080000 Jammed valve in closing
0x00040000 Motor thermostat alarm
0x00020000 Mid-travel alarm OP
0x00010000 Mid travel alarm CL
0x00008000 K1 contactor failure
0x00004000 K2 contactor failure
0x00002000 Alarm extended 5
0x00001000 Alarm extended 6
0x00000800 Alarm extended 7
0x00000400 Alarm extended 8
15
Table 20.
Value
0x80000000 Positioner active
0x40000000 Opened
0x20000000 Closed
0x10000000 Position < = XX%
0x08000000 Position > = YY%
0x04000000 Valve in opening
0x02000000 Valve in closing
0x01000000 Motion inhibited
0x00800000 Open Available
0x00400000 Close Available
0x00200000 Selector in Remote
0x00100000 Monitor relay ON
0x00080000 HW open command active
0x00040000 HW close command active
0x00020000 HW stop command active
0x00010000 HW enabled
0x00008000 Configuration mode
0x00004000 Low alc. battery
38
Element Name
OPERATIONAL_STATUS
Type: BIT_ENUMERATED
Size: 4 octets
Handling: READ
The actuator is fully operational from the fieldbus interface. Details about the current status
are available in the following elements:
Element Name
Installation, Operation and Maintenance Manual
Description
Measured torque greater than the relevant value
configured in torque setup or stroke limits routine.
Measured torque grater than the relevant value
configured in torque set-up or stroke limits routine.
No position change after receiving an Open control
No position change after receiving a Close control.
Motor thermostat open for high temperature
in the motor windings.
The valve does not move in presence of an open control.
The valve does not move in presence of a close control.
The test routine reports a failure of K1 (coil or auxiliary contact).
The test routine reports a failure of K2 (coil or auxiliary contact).
EFS mid-travel alarm (available only in EFS actuator)
Future use
Future use
Future use
Description
The actuator is ready to follow the setpoint from the bus.
Valve in fully open position.
Valve in fully close position.
Valve position less than or equal to a predefined trigger 'xx'.
Valve position greater than or equal to a predefined trigger 'yy'.
Actuator is moving in open direction.
Actuator is moving in closing direction.
In On/Off service:
Set during the Off period when Timer
function is active.
In Modulating service:
Set during the delay time before next
positioning.
Open travelling available
Close travelling available
Local selector on REMOTE position: commands from bus enabled
Monitor Relay Status: actuator available for the remote control
Physical status of the Digital Input #1: Hardwired Open Command
Physical status of the Digital Input #2: Hardwired Close Command
Physical status of the Digital Input #3: Hardwired Stop Command
Physical status of the Digital Input #4: Hardwired Enabled
Configuration mode active
Low alkaline battery
MDE 255 Rev. 0