Emerson Bettis XTE3000 Installation, Operation And Maintenance Manual page 18

Table of Contents

Advertisement

Section 5: F
™ Fieldbus Overview
oundation
January 2022
BIT
15 PST OV-TR
14 PST_ABORTED
13 HI_LO_MAINS
12 WRONG_LIMITS
11 HI_TORQUE
10 MAX_CYCLES_CONTACT
9
8
7
6
5
4
3
2
1
0
14
CONDITION
HI_LO_INT_TEMP
MOTOR_CUR
MAINTEN_REQ
MANUAL_OPER
ESD_ON
INTERLOCK_ON
LOC_STOP_ON
REM_HARDWIRED_OPER
LSEL_OUT_OF_REM
CHECK
Installation, Operation and Maintenance Manual
DESCRIPTION
Position change greater than
x
allowable.
PST cycle aborted due to
x
external condition.
Value of the main voltage out
of the correct range (-15% or
x
+10% of the value stated in the
nameplate menu) or wrong
frequency.
The routine that monitors the
x
stroke limits detects a wrong
end of travel condition.
Measured torque 10% lower
than the relevant value
x
configured in torque setup or
stroke limits routines.
Maximum number of
x
contactor cycles reached.
Temperature inside the
x
actuator enclosure higher than
80 °C or lower than -35 °C.
Motor current greater or lower
x
than limits.
Date of the next maintenance
x
reached.
The actuator is changing the
x
position without electrical
command.
ESD command active
x
(hardwired or from FF).
Interlock open or close active
x
(hardwired or from FF).
x
Local stop button pressed.
Local selector in remote with
x
manual mode enabled.
Local selector not in
x
REMOTE position.
x
Check function.
MDE 255 Rev. 0
RECOMMENDED ACTION
Check PST travel and
parameter OV-TR.
Check if condition to abort
has happened.
Check section of wires
and values of voltage and
frequency.
Recalibrate both stroke limits.
Check the torque necessary to
move the valve.
Change contactor and reset
operation log.
Find the heat source and
insulate the actuator.
Check electrical motor.
Perform maintenance and set
next maintenance date.
Operator is changing the
actuator position
by handwheel.
Check and remove the ESD
condition (C4 pin of terminal
board or FF ESD command).
Check the Interlock condition
(B4 and B5 pin of terminal
board or FF Interlock
command).
Release the Local Stop button.
Check B/HW (C8 connection
on terminal board) signal.
Switch the Local selector
to REMOTE.
Allow ITK to verify operation
of Field Diagnostics.
F
™ Fieldbus Overview
oundation

Advertisement