Emerson Bettis XTE3000 Installation, Operation And Maintenance Manual page 38

Table of Contents

Advertisement

Section 7: Resource Block
January 2022
81
82
83
84
85
86
87
34
FD_CHECK_ALM
Type: DS-87
Size: 15 octets
Handling: READ and WRITE
This parameter is used primarily to broadcast a change in the associated active conditions,
which are not masked, for this alarm category to a Host System.
FD_FAIL_PRI
Type: Unsigned8
Size: 1 octet
Handling: READ and WRITE
This parameter allows the user to specify the priority of this alarm category.
FD_OFFSPEC_PRI
Type: Unsigned8
Size: 1 octet
Handling: READ and WRITE
This parameter allows the user to specify the priority of this alarm category.
FD_MAINT_PRI
Type: Unsigned8
Size: 1 octet
Handling: READ and WRITE
This parameter allows the user to specify the priority of this alarm category.
FD_CHECK_PRI
Type: Unsigned8
Size: 1 octet
Handling: READ and WRITE
This parameter allows the user to specify the priority of this alarm category.
FD_SIMULATE
Type: DS-89
Size: 9 octets
Handling: READ and WRITE
This parameter allows the conditions to be manually supplied when simulation is enabled.
When simulation is disabled both the diagnostic simulate value and the diagnostic value track
the actual conditions. The simulate jumper is required for simulation to be enabled and while
simulation is enabled the recommended action will show that simulation is active.
FD_RECOMMEN_ACT
Type: Unsigned16
Size: 2 octets
Handling: READ
This parameter is a device enumerated summarization of the most severe condition or
conditions detected. The DD help should describe by enumerated action, what should be
done to alleviate the condition or conditions. 0 is defined as Not Initialized, 1 is defined as No
Action Required, all others can be viewed in FD CONDITIONS TABLE.
Installation, Operation and Maintenance Manual
MDE 255 Rev. 0