Installation, Operation and Maintenance Manual
MDE 255 Rev. 0
16
Table 21.
Value
0x8000 High or Low main supply
0x4000 Wrong stroke limits
0x2000 High torque in Opening
0x1000 High torque in Closing
0x0800 Max. contactor cycles
0x0400
0x0200 Motor current
0x0100 Maintenance request
0x0080 Warning extended 1
0x0040 Warning extended 2
0x0020 Warning extended 3
0x0010 Warning extended 4
17
18
19
Resource Block
DIAGNOSTIC_DATA
Type: BIT_ENUMERATED
Size: 2 octets
Handling: READ
The diagnostic information collects the following elements:
Element Name
High or Low internal
temperature
MASK_TOTAL_NOT_OPER
Type: BIT_ENUMERATED
Size: 2 octets
Handling: READ and STATIC WRITE
Default value: 0x0000
This parameter is a mask to create the value of DI channel 32 "Maskable diagnostic status".
Set the bit of TOTAL_NOT_OPER_STATUS that you want to affect the result of channel 32.
MASK_PART_NOT_OPER
Type: BIT_ENUMERATED
Size: 4 octets
Handling: READ and STATIC WRITE
Default value: 0x00000000
This parameter is a mask to create the value of DI channel 32 "Maskable diagnostic status".
Set the bit of PART_NOT_OPER_STATUS that you want to affect the result of channel 32.
MASK_OPERATIONAL
Type: BIT_ENUMERATED
Size: 4 octets
Handling: READ and STATIC WRITE
Default value: 0x00000000
This parameter is a mask to create the value of DI channel 33 "Maskable operational status".
Set the bit of OPERATIONAL_STATUS that you want to affect the result of channel 33.
Description
Main voltage out of the correct range (-15% or +10% of the value stated
in the nameplate menu) or wrong frequency.
The routine that monitors the stroke limits detect a wrong
end of travel condition.
Measured torque 10% lower than the relevant value configured
in torque setup or stroke limit routine.
Measured torque 10% lower than the relevant value configured
in torque setup or stroke limit routine.
Maximum number of contactor cycles reached.
Temperature inside the actuator enclosure higher than 90 °C or lower
than –35 °C.
Motor current greater or lower than limits.
Date of the next programmed maintenance reached.
T-PST value failed
T-RET value failed
OV-TR value failed
PST cycle aborted
Section 7: Resource Block