F136
OUT7 Terminal Assignment
Program Terminal Selection Output Terminal
This parameter sets the functionality of the OUT7 terminals to 1 of the 62
possible functions that are listed in
The on and off delay times of the OUT7 terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
F Input Terminal Delay
Program Terminal Selection In Terminal Delays
This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
R Input Terminal Delay
Program Terminal Selection In Terminal Delays
This parameter delays the response of the drive to any change in the R terminal
input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
ST Input Terminal Delay
Program Terminal Selection In Terminal Delays
This parameter delays the response of the drive to any change in the ST
terminal input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
RES Input Terminal Delay
Program Terminal Selection In Terminal Delays
This parameter delays the response of the drive to any change in the RES
terminal input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
90
Table 16 on pg.
194.
Direct Access Number — F136
Parameter Type — Selection List
Factory Default — Over-Current
Prealarm
Changeable During Run — No
Direct Access Number — F140
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F141
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F142
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F143
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS