F393
Preset Speed Direction #13
Program Pattern Run Preset Speeds
Determines the forward/reverse setting for the #13 Preset Speed (F292).
Settings:
0 — Forward
1 — Reverse
Preset Speed Direction #14
Program Pattern Run Preset Speeds
Determines the forward/reverse setting for the #14 Preset Speed (F293).
Settings:
0 — Forward
1 — Reverse
Preset Speed Direction #15
Program Pattern Run Preset Speeds
Determines the forward/reverse setting for the #15 Preset Speed (F294).
Settings:
0 — Forward
1 — Reverse
Vector Motor Model Autotune Command
Program Motor Parameters Vector Motor Model
This parameter sets the Autotune command status.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
Vector Motor Model Slip Frequency Gain
Program Motor Parameters Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Motor Constant 1 (primary resistance)
Program Motor Parameters Vector Motor Model
This parameter is the measurement of the stator resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
To use Vector Control, Automatic Torque Boost, or Automatic Energy-
Saving, the Motor Constant setting (motor tuning) is required.
HX7+ ASD Installation and Operation Manual
Direct Access Number — F393
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
Direct Access Number — F394
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
Direct Access Number — F395
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — No
Direct Access Number — F400
Parameter Type — Selection List
Factory Default — Autotune Disabled
Changeable During Run — No
Direct Access Number — F401
Parameter Type — Numerical
Factory Default — 0.60
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.55
Direct Access Number — F402
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — No
Minimum — 0.0
Maximum — 100,000 M
Units — 
F402
141