F642
Earth Fault Trip Level
Program Special Control Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Trip activation criteria.
Earth Fault Trip Time
Program Special Control Earth Fault
In the event that the Earth Fault Trip activation criteria is met, a timer begins
to count down to zero. Upon reaching zero, the Earth Fault Trip is activated.
This parameter sets the start-time of the count-down timer.
Acc/Dec Base Frequency Adjustment
Program Terminal Selection Analog In Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Base Frequency. When enabled, either VI/II or RR may be
used as an input source for the modification of the Base Frequency setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Upper Limit Frequency Adjustment
Program Terminal Selection Analog In Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Upper Limit. When enabled, either VI/II or RR may be used
as an input source for the modification of the Upper Limit setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
HX7+ ASD Installation and Operation Manual
Direct Access Number — F642
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100
Units — %
Direct Access Number — F643
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F650
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F651
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F651
175