F216
RX Speed Reference #1
Program Frequency Setting  Speed Reference Setpoints RX
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
RX Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the RX input terminal:
Program Fundamentals Standard Mode Selection Frequency
Mode #1 RX.
Program Fundamentals Standard Mode Selection Command
Mode Use Terminal Board.
Set RX Speed Reference #1 (F216) — the input signal level that
represents RX Speed Frequency #1.
Set RX Speed Frequency #1 (F217).
Set RX Speed Reference #2 (F218) — the input signal level that
represents RX Speed Frequency #2.
Set RX Speed Frequency #2 (F219).
Provide a Run command (F and/or R).
Once set, as the RX input changes, the output frequency of the ASD will vary
in accordance with the above settings.
This parameter sets RX Speed Reference #1 and is the input signal level that is
associated with the setting of RX Speed Frequency #1 while operating in the
Speed Control mode.
RX Input Torque Control Setup
Perform the following setup to allow the system to receive Torque control input
at the RX input terminal:
Program Fundamentals Standard Mode Selection Frequency
Mode #1 RX.
Program Fundamentals Standard Mode Selection Command
Mode Use Terminal Board.
Set RX Speed Reference #1 (F216) — the input signal level that
represents RX Torque Reference Setpoint #1.
Set RX Torque Reference Setpoint #1 (F220).
Set RX Speed Reference #2 (F218) — the input signal level that
represents RX Torque Reference Setpoint #2.
Set RX Torque Reference Setpoint #2 (F221).
Provide a Run command (F and/or R).
Once set, as the RX input changes, the output torque of the ASD will vary in
accordance with the above settings.
This parameter sets RX Speed Reference #1 and is the input signal level that is
associated with the setting of RX Torque Reference Setpoint #1 while
operating in the Torque Control mode.
108
Direct Access Number — F216
Parameter Type — Numerical
Factory Default — 00.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings
Note:
The speed control response
may be further trimmed by
adjusting the Bias and
Gain settings.
Torque Settings
HX7+ ASD Installation and Operation Manual
F216