Installing and cabling the G650 Media Gateway
Connecting the G650 Media Gateway grounds and
other grounds
Follow these additional grounding requirements:
The approved ground wire must be a green / yellow, 10 AWG, copper, stranded wire.
You must bond all approved grounds at the single-point ground to form a single grounding
electrode system.
Connect the cable.
the connection for a single G650 Media Gateway.
Media Gateways
Figure 9: Grounding for a single G650 Media Gateway
Figure notes:
1. 10 AWG (6 mm
30 Installing the Avaya G650 Media Gateway
Figure 9: Grounding for a single G650 Media Gateway
on page 31 shows the connection for two or more G650 Media Gateways.
2
) wire to an approved ground
Figure 10: Grounding for multiple G650
-48 VDC
-48 VDC
RETURN
cadpgrn1 LAO 072403
on page 30 shows
1