Checking the ventilation and the G650 Media Gateway rack

!
WARNING:
Ensure that the area has adequate ventilation. The internal room temperature
WARNING:
must not exceed 104
You must install the G650 Media Gateway in a well-ventilated area. Maximum equipment
performance is achieved at an ambient temperature between 40° and 120° F (4° and 49° C) for
a short-term operation, not more than 72 consecutive hours or 15 days in a year, and up to 104°
F (40° C) for continuous operation. The relative humidity range is 10% to 95% at up to 84 F (29°
C).
For adequate ventilation and to conform with EIA-310D data rack standards, you must provide
the following clearance:
12 inches (30 centimeters) in the rear
18 inches (45 centimeters) in the front
3 inches (7.6 centimeters) on the sides
!
WARNING:
Ensure that the customer-supplied 19-inch (48-centimeter), EIA-310D standard,
WARNING:
open rack is properly installed. The rack must be solidly secured to the floor and
grounded. If the rack is not secured to the floor, do not proceed with the
installation. Avaya does not recommend that you use enclosed data cabinets.
Enclosed cabinets might not allow sufficient ventilation to the G650 Media
Gateway.
!
WARNING:
You must align the G650 Media Gateway with the correct holes in the frame
WARNING:
because the distance between each hole is not uniform. Use the G650/G600
Mounting Template that is shipped with each carrier, to help you align the holes.
Each G650 Media Gateway is 8U high. A typical data rack is 42U high. When you create a
five-carrier G650 Media Gateway stack, all but 3.5 inches (8.9 centimeters) of a typical rack is
used. Mount the A carrier low in the rack.
In a multiple G650 Media Gateway configuration, put the G650s in the rack with no vertical
space between them. If the G650 Media Gateways are not mounted adjacent to one another
with the fronts in the same vertical plane, you cannot use the TDM/LAN cables to connect them.