Section 6.5 Interpreting I/O Error Codes - Spectrum Controls SLC 500 User Manual

Hide thumbs Also See for SLC 500:
Table of Contents

Advertisement

If the module status
LED is...
On
Off
Section 6.5
Interpreting
I/O Error Codes
Table 4-1 LED Definition
Use the following table to interpret LED indications:
And the channel status LED
is...
On
Blinking
Off
Off
I/O error codes appear in word S:6 of the SLC processor status file. The first two
digits of the error code identify the slot (in hexadecimal) with the error. The last
two digits identify the I/O error code (in hexadecimal).
The error codes that apply to your module include (in hexadecimal):
50–5E
71 (watchdog error)
90–94
For a description of the error codes, refer to the Allen-Bradley Advanced
Programming Software (APS) Reference Manual, Allen-Bradley publication
1746-6.11.
Chapter 6: Testing Your Module
Then...
The channel is enabled.
One of the following channel errors occurred:
Circuit open or no wiring is connected.
Signal is near or beyond end of range
Channel configured incorrectly
Refer to Troubleshooting.
Either your module is powering up or the
channel is disabled.
Either the power is off, the module is powering
up, or a module fault occurred. Cycle power. If
the condition persists, call your local distributor
or Spectrum Controls for assistance.