Step 4: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run
capability during this initial charge period.
Step 5: Install software
tshutdown. You may insert the CD provided into the CD-ROM to install the monitoring software.
If not, please follow the on screen instructions to install the software. When your computer restarts, the
monitoring software will appear as an orange plug icon located in the system tray near the clock.
Step 6: External battery connection
This UPS series is not including batteries. Batteries are connected in a separate cabinet with protection.Please
connect external batteries as below chart.
Recommended External Breaker Rating
S. No.
Rating of UPS
1
1 kVA - FM/FMI
2
2 kVA - FM/FMI
3
3 kVA - FM/FMI
7
Battery Breaker
50 A DC (C Curve)
50 A DC (C Curve)
50 A DC (C Curve)
-
+
TO EXTERNAL BATTERY