Interface
07: Bypass voltage range setting
07
HLS
260
I N P U T
BYPASS
08: Autonomy limitation setting
08
M
999
Setting
Parameter 2 & 3: Set the acceptable high
voltage point and acceptable low voltage point
for Bypass mode by pressing the Down key
or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 Vac models:
Vac
230-264: Setting the high voltage point in
Parameter 3 from 230 Vac to 264 Vac.
(Default: 264 Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 Vac models:
170-220: Setting the low voltage point in
Parameter 3 from 170 Vac to 220 Vac.
(Default: 170 Vac)
Parameter 3: Set backup time on battery mode
for general outlets.
0-999: Setting the backup time in minutes from
0-999 for general outlets on battery mode.
0: When setting as '0', the backup time will be
only 10 seconds.
999: When setting as '999', the backup time
setting will be disabled. (Default)