SQ 05.2
SQ 14.2/SQR 05.2
AC 01.2 Non-Intrusive
11.3.1.
Mechanical position indicator: set
11.3.2.
Gear stage of the reduction gearing: test/set
Information
SQR 14.2 Control unit: electronic (MWG)
If options (e.g. potentiometer, position transmitter) are available: Only set mech-
anical position indication once all optional equipment have been successfully set.
1.
Move valve to end position CLOSED.
2.
Turn lower indicator disc until symbol
mark on the cover.
3.
Move actuator to end position OPEN.
4.
Hold lower indicator disc in position and turn upper disc with symbol
until it is in alignment with the
5.
Move valve to end position CLOSED again.
6.
Check settings:
If the symbol
(CLOSED) is no longer in alignment with
Repeat setting procedure.
This test/setting is only required if a different swing angle is subsequently required:
The adjustable swing angle range is available in the order-related technical data
sheet (e.g. "90° +/ 15°").
1.
Pull off indicator disc using a spanner as lever if required.
Commissioning (settings in the actuator)
(CLOSED) is in alignment with the
mark on the cover.
(OPEN)
mark on the cover:
59