AC 01.2 Non-Intrusive
10.4.

Limit switching: set

Select main menu
Select parameter
CLOSED or OPEN
User login
SQR 14.2 Control unit: electronic (MWG)
Valve damage at valve/gearbox due to incorrect setting!
When setting with motor operation: Stop actuator prior to reaching end of travel
(press STOP push button).
For limit seating, provide for sufficient backlash between end position and
mechanical end stop due to potential overrun.
Customer settings M0041
Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
1.
Set selector switch to position 0 (OFF).
2.
Press push button C and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: press
Display indicates: Set end pos.CLOSED?
4.
Select via
Up ▲ Down ▼:
▶ Set end pos.CLOSED? M0084
▶ Set end pos. OPEN? M0085
The black triangle ▶ indicates the current selection.
5.
Press
Ok.
The display indicates either:
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 12
-
Specialist (4) → continue with step 6
6.
Use
Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
7.
Press Ok to confirm selected user.
Display indicates: Password 0***
8.
Enter password (→ enter password).
The display indicates either:
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 12
Commissioning (basic settings)
to parameter, or
and enter ID M0084.
51