Commissioning (basic settings)
Set end position
CLOSED CMD0009
Confirm new end posi-
tion
Set end position OPEN
CMD0010
Confirm new end posi-
tion
Information
10.5.

Test run

52
SQ 05.2
SQ 14.2/SQR 05.2
9.
Set end position CLOSED again :
9.1 For large strokes: Set selector switch in position Local control (LOCAL)
and operate actuator in motor operation via push button
direction of the end position.
Information: Stop actuator before reaching end of travel (press STOP
push button to avoid damage.
9.2 Engage manual operation.
9.3 Turn handwheel until valve is closed.
9.4 Set selector switch to position 0 (OFF).
Display indicates: Set end pos.CLOSED? Yes No
10. Press
Yes to confirm new end position.
Display indicates: End pos. CLOSED set!
The left LED is illuminated (standard version) and thus indicates that the end
position CLOSED setting is complete.
11. Make selection:
Edit → back to step 9: Set end position CLOSED "once again"
Esc → back to step 4; either set end position OPEN or exit the menu.
12. Re-set end position OPEN:
12.1 For large strokes: Set selector switch in position Local control (LOCAL)
and operate actuator in motor operation via push button
direction of the end position.
Information: Stop actuator before reaching end of travel (press STOP
push button to avoid damage.
12.2 Engage manual operation.
12.3 Turn handwheel until valve is open.
12.4 Set selector switch to position 0 (OFF).
Display indicates: Set end pos. OPEN? Yes No
13. Press
Yes to confirm new end position.
Display indicates: End pos. OPEN set!
The right LED is illuminated (standard version) and thus indicates that the end
position OPEN setting is complete.
14. Make selection:
Edit → back to step 12: Set end position OPEN "once again"
Esc → back to step 4; either set end position CLOSED or exit the menu.
If an end position cannot be set: Check the type of control unit in actuator.
Only perform test run only once all settings previously described have been
performed.
SQR 14.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive
(CLOSE) in
(OPEN) in