Wiring diagram, normally closed sensor, option 3C.
Wiring diagram, doorbell.
NOTE:
Option 3C consists of a monitoring system via which the monitor would detect sabotage
in the sensor loop (shorting or cutting the sensor loop).
To enable this option, connect a 2.2KOhm resistor according to the diagram and enable
the 3C function in the monitor (See section 4.3 Alarm settings). A bag with 8 resistors is
included with the wall connector.
Triggering any sensor activates the S output for 5 minutes if the monitor has not been
disarmed, except when configured as a doorbell.
The Z8 sensor input is reserved for the internal tamper (monitor anti-sabotage).

2.5. WIRING OF FERMAX MEET RELAY MODULE REF. 1616

To use the actuator control function, a FERMAX MEET Relay Decoder Ref. 1616 must
be installed.
The connection to the monitor is through the RS-485 connector as shown in the following diagram.
To activate the devices to be controlled, use the relay outputs 1 to 8, corresponding to the
activations R1 to R8 of the monitor control screen. Relay outputs 0 and 9 are not used.
The module Ref. 1616 is powered directly from the monitor. No additional power is required.
The address of module has to be No.1 (this is the factory value).
NOTES
The module Ref. 1616 only activates the corresponding relay during the time indicated in the
programming (between 1 and 60 seconds). After this time, the relay automatically returns to
standby.
No relay status is displayed on the monitor.