5.3.2 Power supply
DO
Digital output 24 VDC
DI
Digital input 24 VDC
0V
Reference potential GND
FE
Functional earth
V+
+24 VDC ± 20%
Conductor cross sections: V+ / FE / 0V: AWG 18 (≙ 0.75 mm
The permissible voltage ranges and the maximum values for the current and power
consumption can be found in Section 12 Technical Data.
5.3.3 Digital inputs and outputs
Digital output: type 3 according to IEC61131 (no self-diagnostic function)
0 signal = 0 V, 1 signal = 24 VDC, max. 30 mA.
Reverse voltage polarity protection. Automatic restart after fault state (e.g. after short circuit at
output).
Digital input: type 3 according to IEC61131.
0 signal = 0...+5 VDC; 1 signal = +11...+30 VDC, max. 2.7 mA.
Schematic circuit diagram:
The digital inputs and outputs can be assigned functions in the Configuration Center.
© ads-tec Industrial IT GmbH • Heinrich-Hertz-Str. 1 • 72622 Nürtingen • Germany
DO DI 0V FE V+
(The figure shows the socket inside the device)
)