Emerson EV2000 Series User Manual page 63

Universal variable speed drive
Table of Contents

Advertisement

Upper limit of
freq. F
H
Central Freq. Fset
Lower limit of freq. F
Preset freq.
Run
command
stop
command
The central frequency is actually the preset frequency of simple operation (except PLC, traverse operation, jog),
multi-step speed operation or PLC operations;
Traverse operating function is disabled automatically in Jog operation or close-loop operation process.
If PLC operation and traverse operation start at the same time, the traverse operation is disabled when the drive transits
from one PLC operating stage to another stage. The drive will accelerate to the preset frequency of PLC operation and
then start traverse operation. The drive will decelerate to stop within the Dec time set in PLC operating stage.
F6.00 Traverse function selection
F6.00 decides whether the traverse operating function is
enabled
0: disabled
1: enabled
F6.01 Traverse operating mode
F6.01 is used to set the traverse operating mode and
the meanings of LED display are shown in Fig. 5-38.
Operating
freq. (Hz)
Traverse operation
amplitude Aw=Fset*F6.04
+ Aw
- Aw
a1
L
Jitter
freq.=AW*F6.05
a1
Waiting time
Accelerate
F6.03
according
to Acc time
Fig. 5-37 Traverse operation
Range:0~1 【 0 】
Range:0000~1111
【 0000 】
EV2000 Series Universal Variable Speed Drive User Manual
Chapter 5 Parameter Introductions
Rising
time=F6.06*F6.07
Traverse
operating
cycle
A
C
B
D
Fig. 5-38 Traverse operating mode
Where,
A: thousand's place
C: Ten's place
Unit's place: start mode
0: auto mode
t
Decelerate
according
to Dec time
Start mode:
1: Auto start
2: Manual start mode
Traverse operating amplitude control
1: Variable amplitude
2: Fixed amplitude
Restart mode
1: Restart at the freq. and direction
memorized before stopping
2: Restart
Save parameters upon power outage
1: Save
2: Not save
B: Hundred's place
D: Unit's place
59