Starting And Braking Parameters (Group F2) - Emerson EV2000 Series User Manual

Universal variable speed drive
Table of Contents

Advertisement

① Use the pulse signal input via terminal to set the
reference frequency;
② Range of input signal frequency:1kHz~20kHz;
③ 1kHz input signal corresponds to 50Hz reference
frequency, and 20kHz input signal corresponds to 5Hz
reference frequency;
According to the above requirements, the parameter
settings are:
① F0.00=5, select pulse input to set the reference
frequency;
② F7.06=45, input pulse signal via terminal X7;
③ F1.00=100, select curve 2;
④ F1.03=20.0kHz, set the Max input pulse frequency to
20kHz;
⑤ F1.08=1÷20×100%=5.0%, the minimum reference of
curve 1 is actually the percentage of 1kHz to
20kHz(F1.03);
⑥ F1.09=50.00Hz, set the frequency that corresponds to
the Min reference (1kHz pulse signal);
⑦ F1.10=20÷20×100%=100.0%, the Max reference of
curve 2 is actually the percentage of 20kHz to
20kHz(F1.03);
⑧ F1.11=5.00Hz, set the frequency that corresponds to
the Max reference (20kHz pulse signal);
frequency
Output
F1.09=50
F1.11=5
F1.08=5
F0.00=5, F1.00=100, F1.03=20, F7.06=45
Fig. 5-10 Pulse signal input
5.3 Starting and Braking Parameters
(Group F2)
F2.00 Starting mode
0: Start from the starting frequency
Start at the preset starting frequency (F2.01) within the
holding time of starting frequency (F2.02).
1:Brake first and then start
Pulse signal input
F1.10=100
Range:0. 1. 2 【 0 】
EV2000 Series Universal Variable Speed Drive User Manual
Chapter 5 Parameter Introductions
Brake first(refer to F2.03 and F2.04), and then start in
mode 0.
2. Start on the fly
Search and catch the motor's running direction and
speed, start the rotating motor smoothly without impact,
as shown in Fig. 5-11.
AC supply
On
Motor speed
0
Drive's
Run reverse
output freq.
without load
Forward
Drive's running
direction
Fig. 5-11 Start on the fly
Notes:
1. Starting mode 1 is suitable for starting the motor that is
running forward or reverse with small inertia load when the
drive stops. For the motor with big inertial load, it is
recommended to use starting mode 2;
2. The starting performance of starting mode 2 is dependent
on the motor's parameters. Please set the parameter group
FH correctly.
3. Starting mode 0 is recommended when the drive drives a
synchronous motor.
F2.01 Starting frequency
F2.02 Holding time of starting
frequency
Starting frequency is the initial frequency when the drive
starts, as shown in Fig. 5-12 as f
starting frequency is the time during which the drive
operates at the starting frequency, as shown in Fig. 5-12
as t
1
Frequency
Hz
f
max
f
s
t
1
Fig. 5-12 Starting frequency and starting time
OFF
ON
Reverse
Detect motor's speed
and direction
Range:0.20~60.00Hz
【 0.50Hz 】
Range:0.0~10.0s 【 0.0s 】
; Holding time of
S
Time
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents