Emerson EV2000 Series User Manual page 33

Universal variable speed drive
Table of Contents

Advertisement

Category
Terminal
P24
+24V power supply
Common terminal of
PLC
multi-function input
terminal
Power
Common terminal of
supply
COM
+24V power supply
Common terminal of Y1
CME
and Y2 output
Shielding
PE
Shielded GND
1) Wire connections multi-function input terminals,
terminals FWD and REV:
EV2000 multi-function input terminal uses a full-bridge
rectifying circuit as shown in Fig. 3-. PLC is the common
terminal of terminals X1~X8, FWD and REV. The current
flows through terminal PLC can be pulling current, and
also the feeding
current.
and REV is flexible and the typical wiring is shown
below:
A) Method 1 of connections (Dry contacts)
①If internal 24V power supply is used, the wiring is
shown in Figure 3-22.
+24V
P24
PLC
power
source
R
K
X1 X2 . . . X8
FWD REV
COM
Fig. 3-22 Using internal 24V power supply
②If an external power supply is used, then use the Wire
connections shown in Fig. 3-23. (be sure to disconnect
the cable between P24 and PLC)
Name
Provide +24V power supply for
external equipment.
Common terminal of multi-function
input terminal (short circuit with P24)
Total 3 common terminals, which are
used in conjunction with other
terminals.
Common terminal of multi-function
Y1 and Y2 output
(Short circuit with COM by
manufacturer)
Grounding terminal connected to
shielding layer
Wire connections X1~X8, FWD
+5V
+
-
EV2000
EV2000 Series Universal Variable Speed Drive User Manual
Chapter 3 Installation and Wiring
Functions
Maximum output current:
200mA
Common terminal of X1~X8.,
FWD and REV. PLC is isolated
with P24.
COM is isolated with CME and
GND.
Connected to PE inside the
drive
+24V
P24
PLC
+
power
DC
-
R
K
X1 X2 . . . X8
FWD REV
COM
Fig. 3-23 Using an external supply
B). Method 2 of connections
①Drive's internal +24V power supply is used and the
external controller uses NPN transistors whose common
emitters are connected, as shown in Figure 3-24.
External controller
1
10
COM
shielded cable's end near the drive
should be connected to the PE
Fig. 3-24 Method 2 of connections(a)
29
Specifications
+5V
+
-
EV2000
EV2000
D2
P24
+
5V
COM
24V DC
-
PLC
FWD
5V
X8
PE

Hide quick links: