2. Wire Connections of Drive for Basic Operation
Models: EV2000-4T0055G/0075P. EV2000-4T0075G/0110P
3-phase
380V
50/60Hz
Forward/stop
Reverse/stop
Multi-function input 1
Multi-function input 2
Multi-function input 3
Multi-function input 4
Multi-function input 5
Multi-function input 6
Multi-function input 7
Multi-function input 8
Speed command
0~10V
0 10V/0 20mA
Notes:
1. Terminal CCI can be input voltage or current signal by switching the jumper CN10 on control board;
2. The auxiliary power supply comes from the bus (+) and bus (-);
3. Built-in braking kit is installed and a braking resistor is required to be connected between (+) and PB;
4. In the above figure, "O" is the terminal in main circuit, and "⊙" is the control terminal;
5. Refer to section 3.3.2 for the using of control terminals.
DCL DC reactor
(connect optional parts
externally)
P1
Breaker
R
R
S
S
T
T
P24
PLC
FWD
REV
X1
X2
X3
X4
X5
X6
X7
X8
COM
VRF
VCI
CCI
.
.
GND
CN10
PE
Fig. 3-9 Basic wiring 1
EV2000 Series Universal Variable Speed Drive User Manual
Braking resistor
(connect optional parts
externally)
(-)
(+)
PB
Aux.
P24
Power
COM
supply
X7
X8
PE
.
GND
0/4 20mA
.
.
0 10V
AO1
CN16
.
AO2
0/4 20mA
.
.
0 10V
P24
DO
CN17
COM
Y1
EV2000
Y2
CME
COM
.
I
V
485+
485-
.
RS232
.
TXD
.
RS485
RXD
CN14
GND
Chapter 3 Installation and Wiring
U
V
M
W
PE
PG
DC current
meter
0/4-20mA current
signal
Output 0-24V pulse
signal
Frequency meter
Output 1
Bi-direction open
collector output
Output 2
Common terminal
TA
Programmable
TB
relay output
TC
RS485
communication port
RS232
communication
port