Note:
Different with No. 6~7 functions, the external stopping
signal will not trigger alarm and the drive can resume
normal operation after the signal is removed.
19: DC injection braking signal
If the setting is 19, the terminal can be used to perform
DC injection braking to the motor that is running so as to
realize the emergent stop and accurate location of the
motor. Initial braking frequency, braking delay time and
braking current are defined by F2.09~F2.11. Braking
time is the greater value between F2.12 and the
effective continuous time defined by this control
terminal.
20: disabling close-loop function
If the setting is 20, the terminal can be used to realize
the flexible switching between close-loop operation and
low level operating mode (refer to section 4.1.4 for
details).
Note:
The switching between operation modes is enabled only in
close-loop operation (F5.00=1).
When the drive is switched to low level operating mode,
its start/stop, operating direction, ACC/Dec time should
be compliant with corresponding operating modes.
21: disabling PLC
If the setting is 21, the terminal is used to realize the
flexible switching between PLC operation and low level
operating mode (refer to section 4.1.4 for details).
Note:
The switching between operation modes can be enabled
only in PLC operation (unit's place of F4.00 is not 0).
When the drive is switched to low level operating mode,
its start/stop, operating direction, ACC/Dec time should
be compliant with corresponding operating modes
accordingly.
22~24: Terminals 1~3 for reference frequency selector.
Different ON/OFF combinations of terminals 1, 2 and 3
can select different reference frequency selectors as
shown in Table 5-8. The drive will act to the command
from the terminal or F0.00, whichever comes late.
Table 5-8 Frequency selector
Terminal 3 Terminal 2 Terminal 1
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
Freq. selector
OFF
Hold the setting
ON
Digital setting 1
OFF
Digital setting 2
ON
Digital setting 3
OFF
VCI analog input
EV2000 Series Universal Variable Speed Drive User Manual
Chapter 5 Parameter Introductions
Terminal 3 Terminal 2 Terminal 1
ON
OFF
ON
ON
ON
ON
25:Frequency reference is input via terminal CCI forcibly
If the setting is 25, the frequency reference will be input
via terminal CCI forcibly. The frequency selector will be
changed to the previous one if this terminal function is
disabled.
26:Reserved
27: Terminal control mode is forcibly enabled
When this terminal function is enabled, the operating
command is input through this terminal forcibly, and the
drive will be controlled in previous control mode if
FWD/REV terminal function is disabled.
28~29: On/Off combinations of terminals 1 and 2 for
different control modes selection
Table 5-9 Control modes
Terminal 2
Terminal 1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
The control modes in Table 5-9 can be selected by the
different On/Off combinations of terminals 1 and 2.
30~32: Selecting preset close-loop reference
frequencies via On/Off combinations of terminals 1~3.
Table 5-10 Preset close-loop reference selection
Terminal 3 Terminal 2 Terminal 1
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
Freq. selector
ON
CCI analog input
PULSE terminal
OFF
input
PULSE terminal
ON
input
Control modes
Hold the control mode
Panel control mode
Terminal control mode
Serial port control mode
Preset close-loop
reference selection
Close-loop reference
is decided by F5.01
Preset close-loop
reference 1
Preset close-loop
reference 2
Preset close-loop
reference 3
Preset close-loop
reference 4
Preset close-loop
reference 5
Preset close-loop
reference 6
Preset close-loop
reference 7
63