Chapter 6 Troubleshooting
Fault
Fault categories
code
Protections of
E010
IGBT act
IGBT module's
E011
heatsink
overheat
Rectifier's
E012
heatsink
overheat
E013
Drive overload
E014
Motor over-load
Emergent stop
E015
or external
equipment fails
EEPROM R/W
E016
fault
Possible reasons of fault
Instantaneous over-current
Short-circuit among 3-phase output or
line-to-ground short circuit
Vent is obstructed or fan does not work
Over-temperature
Wires or connectors of control board are loose
Current waveform distorted due to output
phase loss
Auxiliary power supply is damaged or IGBT
driving voltage is too low
Short-circuit of IGBT bridge
Control board is abnormal
Over-temperature
Vent obstructed
Fan does not work
IGBT module is abnormal
Ambient over-temperature
Obstruction of ventilation channel
Fan does not work
Too short Acc/Dec time
DC injection braking current is too big
Improper V/F curve
The rotating motor restart after the drive stops
instantly.
Low AC supply voltage
Too heavy load
Improper V/F curve
Low AC supply voltage
Common motor has operated with heavy load
at low speed for a long time.
Improper motor's overload protection threshold Modify the motor's overload protection
Load changes fast
STOP is pressed in non-panel control mode
STOP pressed when the drive is in stall status
The drive will report E015 fault if it is in stall
status for 1 minute
Terminal used for stopping the drive in
emergent status is closed
R/W fault of control parameters
EV2000 Series Universal Variable Speed Drive User Manual
Actions
Refer to E001~E003
Rewiring
Clean the vent or replace the fan
Lower the ambient temperature
Check and rewiring
Check the wiring
Seek service
Seek service
Seek service
Lower the ambient temperature
Clean the vent
Replace the fan
Seek service
Lower the ambient temperature
Clear the ventilation channel
Replace the fan
Prolong the Acc/Dec time
Reduce the DC injection braking current
or prolong the braking time
Adjust V/F curve or torque boost value
Set the starting mode (F2.00) to "start of
fly"
Check the AC supply voltage
Select the drive with bigger power
Set V/F curve and torque boost value
correctly
Check the AC supply voltage
Use a special motor if the motor is
required to operate for a long time.
threshold.
Check the load
Check the definition of STOP function in
F9.07 and the operating mode
Check the definition of STOP function in
F9.07
Set FL.02 and FL.03 properly
Disconnect the terminal if the external
fault is cleared
Press STOP/RESET to reset
Seek service