Code 2
(cont.)
Coding in the delivered condition
Room temperature sensor offset
E2:50
Available if code "A0:1", "A0:2" or
"A0:3", "Heating" group, is set.
No correction of actual room tem-
perature
Screed drying
F1:0
Screed drying not active
DHW (DHW heater)
Coding
Coding in the delivered condition
Set DHW temperature reheating suppression
67:0
Reheating suppression of solar
control unit deactivated
Start hysteresis, DHW
85:0
Pump on: As soon as DHW
DHW
set
Controllers
Note
Changing the controllers is only permitted following
consultation with the manufacturer.
<
actual
- 2.5 K
Possible change
E2:0
Correction - 5 K to display correction
to
- 0.1 K
E2:49
E2:51
Display correction + 0.1 K to display
to
correction + 4.9 K
E2:99
F1:1
Screed drying adjustable, with
to
choice of 6 temperature/time pro-
F1:6
files.
For further information, see chapter
"Screed drying"
Possible change
67:1
DHW set value during active reheat-
to
ing suppression of the solar control
67:90
unit in °C
85:1
Setting range in K
to
Pump on: As soon as DHW 1 to
85:10
10 K below WW
Codes
set
97