Viessmann Vitoligno 300-C Installation And Service Instructions Manual page 84

18 to 48 kw pellet boiler
Table of Contents

Advertisement

Codes
Code 1
(cont.)
Buffer (heating water buffer cylinder)
Coding
Coding in the delivered condition
Buffer cylinder temperature reheating suppression
33:0
Reheating suppression disabled
Maximum buffer cylinder temperature
34:...
Maximum average temperature of
the heating water buffer cylinder
(upper limit of control range)
Minimum buffer cylinder temperature
35:...
Minimum average temperature of
the heating water buffer cylinder
(lower limit of control range)
Buffer cylinder charging to sensor
36:3
The boiler charges the heating wa-
ter buffer cylinder up to buffer tem-
perature sensor 3.
Buffer cylinder charging up to temperature
37:...
The boiler charges the heating wa-
ter buffer cylinder up to a tempera-
ture of ... °C at the selected sensor
(code "36:1-5", buffer cylinder
group) is reached.
Boiler start, sensor
39:1
If the set system temperature at
buffer temperature sensor 1 (top)
is undershot, the boiler starts.
Additional heat generator
Available if code "Additional boiler" is set to "Yes".
84
Possible change
33:1
Set temperature of the heating water
to
buffer cylinder for solar charging.
33:100
Setting range in °C
34:30
Setting range in °C
to
34:100
35:30
Setting range in °C
to
35:100
36:1
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 1 (top).
36:2
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 2.
36:4
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 4.
36:5
The boiler charges the heating water
buffer cylinder up to buffer tempera-
ture sensor 5.
37:30
Setting range in °C
to
37:100
39:2
If the set system temperature at buf-
fer temperature sensor 2 is under-
shot, the boiler starts.
39:3
If the set system temperature at buf-
fer temperature sensor 3 is under-
shot, the boiler starts.
39:4
If the set system temperature at buf-
fer temperature sensor 4 is under-
shot, the boiler starts.
39:5
If the set system temperature at buf-
fer temperature sensor 5 is under-
shot, the boiler starts.
For code "Additional boiler", see Hardware group.