Viessmann Vitoligno 300-C Installation And Service Instructions Manual page 111

18 to 48 kw pellet boiler
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed fault
System characteristics
code
D6
Warning
D8
Warning
E0
Burner locked out
F7
Burner locked out
F8
Burner locked out
F9
Burner locked out
FA
Burner locked out
FF
Boiler output deviating
Cause
The silo may not be full
enough
CAN bus interruption
Jumpers are not inserted
in slots 97 and 98
Heat exchanger cleaning
did not reach limit position
Ash removal screw con-
veyor has gone into re-
verse too often
Grate did not reach limit
position
Proximity switch in pellet
hopper is constantly dirty
Program memory error
Troubleshooting
Measures
Check the silo fill level
Check fuses
Check wiring
Check jumpers and insert if neces-
sary
Check the limit switch for heat
exchanger cleaning
Check heat exchanger cleaning
Check ash removal screw convey-
or and ash box
Acknowledge a fault
If fault recurs, check grate
Clean grate if necessary
Clean proximity switch
Check boiler type in the control unit
111