Filling The Heating System; Checking All Connections On The Heating Water Side For Leaks - Viessmann Vitoligno 300-C Installation And Service Instructions Manual

18 to 48 kw pellet boiler
Table of Contents

Advertisement

Filling the heating system

Fill water
!
Please note
Unsuitable fill water increases the level of
deposits and corrosion, and may lead to system
damage.
Flush the heating system thoroughly before
filling.
Only fill with water of potable quality.
Special antifreeze suitable for heating systems
can be added to the fill water. The antifreeze
manufacturer must verify its suitability.
Fill and top-up water with a water hardness in
excess of the following values must be soft-
ened, e.g. with a small softening system for
heating water.
Total permissible hardness of the fill and top-up water
Total heating output
kW
50
50 to 200
Fig. 34
1. Check the pre-charge pressure of the expansion
vessel.
If the pre-charge pressure is lower than the static
system pressure, top up with nitrogen until the pre-
charge pressure is 0.1 to 0.2 bar (10 to 20 kPa)
higher than the static system pressure.
If the pre-charge pressure is too high, adjust it
accordingly.

Checking all connections on the heating water side for leaks

Specific system volume
< 20 l/kW
3
3.0 mol/m
(16.8 °dH)
3
2.0 mol/m
(11.2 °dH)
Commissioning, inspection, maintenance
20 l/kW to < 50 l/kW
3
2.0 mol/m
(11.2 °dH)
3
1.5 mol/m
(8.4 °dH)
2. Open the non-return valves.
3. Fill the heating system with water. Then bleed until
the charge pressure is 0.1 to 0.2 bar (10 to 20 kPa)
higher than the pre-charge pressure of the expan-
sion vessel.
Permissible operating pressure: 3 bar (0.3 MPa)
Test pressure: 4 bar (0.4 MPa)
4. Mark the charge pressure at pressure gauge
5. Reset the non-return valves to their operating posi-
tion.
50 l/kW
3
< 0.02 mol/m
(0.11 °dH)
3
< 0.02 mol/m
(0.11 °dH)
.
A
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vl3c

Table of Contents