13. TECHNICAL SPECIFICATIONS

Type ................................................................................. EXPERT-PN110
Main supply fuse F1 ........................................................... 4A, slow-blow
Mains supply/frequency ..................................................... 90-240VAC 50/60Hz 30W Max
0-10V outputs 1-2 ............................................................. 0-10Vdc, 30mA source max.
Precision on 0-10V outputs ................................................ ±1 %
14Vdc output .................................................................... 14 Vdc ±10%, regulated, 250mA max.
Alarm contact ................................................................... ON/OFF output, 24VDC or AC, 0.15A
Housing ............................................................................ IP54, plastic casing
Operating temperature ....................................................... 32 to 104°F (0 to 40°C)
Storage temperature .......................................................... 5 to 122°F (-15 to 50°C)
Ambient relative humidity................................................... max. 95%
Pot + output .................................................................... 3.0V, 20mA max.
Potentiometer inputs .......................................................... 1-20K pot., linear
RH input ........................................................................... 4-20mA
Pressure input ................................................................... 4-20mA
Temperature inputs ............................................................ 1K @ 77°F (25°C), NTC
Relays ............................................................................. 240Vac, 50/60Hz, 15A res.
Variable 1,2: .................................................................... 50/60Hz, 1/2HP (373W) @ 120Vac,
Fuse on variable outputs .................................................... 15A slow blow
The room temperature where the con-
troller is located must always remain
between 32 °F and 104 °F (0 °C
and 40 °C).
6FLA, 1HP (746W) @ 120Vac, 50/60Hz
12FLA, 2HP (1490W) @ 240Vac, 50/60Hz
Max tungsten(light bulb): 8.3A @ 120Vac
1 1/2HP (1120W) @ 240Vac, 10A max
EXPERT PN110 rev.23