0-10V Ventilation Outputs - Airstream EXPERT PN110 User Manual

Table of Contents

Advertisement

EXPERT PN110

6.2.3. 0-10V Ventilation Outputs

The controller has two 0-10V outputs that can
either be used to control heaters or fans. To
operate these outputs, the controller refers
to the average temperature reading of their
assigned temperature probes (sec. 4.7.3).
This section explains how 0-10V ventilation
outputs work.
The 0-10V ventilation outputs start at their
minimum intensity when the average tem-
perature of their probes reaches the start
temperature. They increase in intensity as
the temperature increases; 0-10V outputs
reach their maximum intensity when the tem-
perature rises to the "Maximum Temperature"
parameter setting.
0-10V Ventilation
Intensity
Output
Max
Min
OFF
Stop T°
Start T°
1. Select:
» START / STOP TEMPS
5. 0-10V Outputs
»
» Select the desired 0-10V Output
* This menu is accessible if a 0-10V output is enabled
(sec. 4.5).
Start Temp 75.0°F
Min:
10 Max:
Max Output at: 72.5
Stop at:
2. Set the following parameters:
Start temperature — Set the start tempera-
ture to the desired value.
Minimum & max speeds — Set the minimum
and maximum speeds of the 0-10V output.
The maximum speed must be greater than
the minimum speed.
Maximum output at — Set the temperature at
which the output reaches its maximum speed
(this parameter must be set to a greater value
than the start temperature).
Max
Avg T°
Stop at — This is the temperature below
of 0-10V
which the 0-10V output stops.
output
probes
100
70.0
EXPERT PN110 rev.23
19