EXPERT PN110
6.6.

Misting Output

To operate the misting output, the controller
refers to the average reading of the tempera-
ture probes assigned to the output.
The controller can control one misting out-
put. When the temperature reaches the start
temperature of the output, mist units are
activated and run in timer mode according to
their minimum timer (Min On Time & Min Off
Time). Then, as temperature rises, a gradual
transition is made from the minimum timer
towards the maximum timer (Max On Time
& Max Off Time). The second mist timer is
fully used when the temperature reaches the
Maximum Temperature parameter setting.
The misting output is disabled when the
temperature falls below a user-defi ned value.
It can also stop when humidity levels are too
high (see RH Compensation in chapter 10).
Misting
Mist
Timer
Output
Max On
Time
Min On
Time
OFF
OFF T°
ON T°
1. Select:
» START / STOP TEMPS
» 7. Cooling*
*This parameter is acessible if the cooling output is
enabled (see sec. 4.5).
Cooling
On Temp
Off Temp
Min.OnTime
Off Time
Max.Temperature 87.0
Max.OnTime
2.
Set the following parameters:
On Temp. / Off Temp — Select the tempera-
ture at which the cooling output starts and
stops.
Min/Max On Time — Set the minimum and
maximum On Time of the cooling timer.
Max Temperature — Set the temperature at
which the cooling output uses its maximum
timer settings. The maximum temperature
must be at least 0.5°F (0.3°C) greater than
the ON TEMP.
Max T°
85.0
83.0
15sec
900sec
180sec
6.7.

Soaking

The soaking output is used to clean the room
when it is empty. This output runs in timer
mode when the controller is in clean mode.
1. Select:
» START / STOP TEMPS
» 9. Soaking*
*This parameter is acessible if the soaking output is
enabled (see sec. 4.5).
On Time:
60sec
Off Time:
60min
#Soaking Cycle: None
2. Set the following parameters:
On/Off Time — Set the timer used by the
soaking output.
# Soaking Cycles — Select how many soak-
ing cycles must be performed from the mo-
ment the controller enters in clean mode (1
to 100 cycles).
EXPERT PN110 rev.23
27