INTER 2V4SA
9. 

Misting

The last cooling stage can be used as a mist
stage. Set internal switch #9 to ON to acti-
vate this stage. The number of heating stages
determines which stage is used for misting:
Number of heating 
stages
0
1
2
The mist stage cannot be used if two
heating stages are used.
• Mist units start running according to a
timer cycle (On Time and Off Time) when
their start temperature is reached (Set Point
+ Mist Offset + Differential).
• If the humidity compensation is activated,
mist units automatically stop when the hu-
midity level is too high.
Operating Diagram of 
Mist 
the Mist Output
Output
Status
On
Off
Mist Offset
Set Point
26
INTER 2V4SA, rev.02
Mist stage =
Stage 6
Stage 5
Stage 4
Room T°
Differential
I.  Adjusting the Mist Differential
The mist differential is the variation in room
temperature between the moment mist units
turn on and the moment they turn off. It
can be adjusted between 0,3°C and 10,0°C
(0,5°F and 18,0°F).
• Select the MIST  OFFSET/DIFFERENTIAL 
menu.
• Press the Other Functions button. The mist
differential is displayed, alternating with the
letters "dIF",
• Use the adjustment buttons to set it to the
desired value.
II.  Adjusting the Mist Offset
The mist offset tells the controller when to
stop the mist stage (Set Point + Mist Offset).
It can be adjusted between 0,3°C and 22,0°C
(0,5°F and 40,0°F).
• Select the MIST  OFFSET/DIFFERENTIAL 
menu. The mist offset is displayed, alternat-
ing with the letters "OFSEt".
• Use the adjustment buttons to set it to the
desired value.
III.  Adjusting the Mist Timer
The On Time of the mist timer can be adjusted
from 0 to 900 seconds, in increments of 15
seconds; the Off Time can be adjusted from
0 to 60 minutes. To disable mist cooling, set
the On Time to zero.
• Select the MIST TIMER menu. The current
On Time for the mist cycle is displayed, al-
ternating with the letters "t On".