Closed-Loop Crimp Terminals - YASKAWA CR700 Quick Start Manual

Ac drive
Hide thumbs Also See for CR700:
Table of Contents

Advertisement

Model
Terminal
R/L1, S/L2, T/L3, R1/L11, S1/
L21, T1/L31
U/T1, V/T2, W/T3
4414
-, +1
+3
R/L1, S/L2, T/L3, R1/L11, S1/
L21, T1/L31
U/T1, V/T2, W/T3
4453
-, +1
+3
R/L1, S/L2, T/L3, R1/L11, S1/
L21, T1/L31
U/T1, V/T2, W/T3
4605
-, +1
+3
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than AWG 8, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lbf∙in to 40 lbf∙in).
*4
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5
A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.

Closed-Loop Crimp Terminals

To comply with UL standards on drive models 2215 to 2415 and 4180 to 4605, use UL-approved closed-loop
crimp terminals. Use the tools recommend by the terminal manufacturer to crimp the closed-loop crimp terminal.
Yaskawa recommends closed-loop crimp terminals from JST Mfg. Co., Ltd. and insulation caps from Tokyo DIP
Co., Ltd. Contact Yaskawa or your nearest sales representative to make an order.
Refer to
Table 16.4
to select crimp terminals as specified by drive model and wire gauge.
Note:
To comply with UL standards, use only insulated crimp terminals or crimp terminals with insulation tubing. Use UL-Listed, vinyl-
coated insulated copper wires for operation with a continuous maximum permitted temperature of 75 °C at 600 V.
Recomm. Gauge (AWG, kcmil)
Model
R/L1, S/L2,
U/T1, V/T2,
T/L3
W/T3
2003 - 2018
-
2025, 2033
-
2047
-
2060 - 2088
-
2115
-
YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
Applicable
Gauge
Recomm. Gauge
(IP20 Applicable
AWG, kcmil
Gauge
AWG, kcmil
2/0 - 300 × 4P
250 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
4/0 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
4/0 × 4P
(300 - 400 × 4P)
2 - 4/0
3/0 × 4P
(4/0 × 4P)
1/0 - 300
1/0
2/0 - 300 × 4P
250 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
4/0 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
300 × 4P
(300 - 400 × 4P)
2 - 4/0 × 4P
3/0 × 4P
(4/0 × 4P)
2/0 - 300
2/0
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
2/0 - 300 × 4P
300 × 4P
(250 - 300 × 4P)
3/0 - 400 × 4P
400 × 4P
(300 - 400 × 4P)
2 - 4/0 × 4P
4/0 × 4P
(4/0 × 4P)
2/0 - 300
2/0
Table 16.4 Closed-Loop Crimp Terminals and Insulation Caps
-, +1
+3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Wire Stripping
*2
Length
*1
)
mm
-
-
-
-
-
(-)
-
-
-
-
-
(-)
-
-
-
-
-
(-)
Crimp
Terminal
Terminal
Screw Size
Model
10
M4
R5.5-4
8
M5
R8-5
6
M6
R14-6
6
M6
R14-6
4
M6
R22-6
16 UL Standards
Terminal Screw
Tightening
Size
Shape
N∙m (lbf∙in)
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex bolt (slotted)
(283 - 354)
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex bolt (slotted)
(283 - 354)
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex bolt (slotted)
(283 - 354)
Crimping Tool
Tool Model
Die Jaw
YA-4
AD-900
YA-4
AD-901
YA-4
AD-902
YA-4
AD-902
YA-5
AD-953
Torque
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
EN
Insulation
Cap Model
TP-005
TP-008
TP-014
TP-014
TP-022
113