L1-02: Motor Overload Protection Time; L1-03: Motor Thermistor Oh Alarm Select - YASKAWA CR700 Quick Start Manual

Ac drive
Hide thumbs Also See for CR700:
Table of Contents

Advertisement

16 UL Standards
Load Tolerance

L1-02: Motor Overload Protection Time

No.
Name
(Hex.)
L1-02
Motor Overload Protection
Time
(0481)
Set the overload tolerance time to the length of time that the motor can operate at 150% load from continuous
operation at 100% load.
When the motor operates at 150% load continuously for 1 minute after continuous operation at 100% load (hot
start), the default setting triggers the electronic thermal protector.
Figure 16.6
shows an example of the electronic thermal protector operation time. Motor overload protection
operates in the range between a cold start and a hot start.
This example shows a general-purpose motor operating at the base frequency with L1-02 set to 1.0 min.
• Cold start
Shows the motor protection operation time characteristics when the overload occurs immediately after starting
operation from a complete stop.
• Hot start
Shows the motor protection operation time characteristics when overload occurs from continuous operation
below the motor rated current.
Figure 16.6 Protection Operation Time for a General-purpose Motor at Rated Output Frequency

L1-03: Motor Thermistor oH Alarm Select

No.
Name
(Hex.)
L1-03
Motor Thermistor oH
Alarm Select
(0482)
0 : Ramp to Stop
The drive ramps the motor to stop according to the deceleration time. Fault relay output terminal MA-MC will
turn ON, and MB-MC will turn OFF.
120
Cooling Capability
This motor is designed to operate with commercial line
power. Operate at a 50 Hz base frequency to maximize
the motor cooling ability.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the
motor. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation when the PTC input signal to the drive is at the oH3 [Motor Overheat
(PTC Input)] detection level.
YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
Overload Characteristics (at 100% motor load)
If the motor operates at frequencies less than commercial
line power, the drive will detect oL1. The drive triggers a
fault relay output and the motor coasts to stop.
Description
Description
Default
(Range)
1.0 min
(0.1 - 5.0 min)
Default
(Range)
3
(0 - 3)