Checking the Equipment Operational Status

Executes a sampling and displays management points operating out of the set up operation
rules. The checking results can also be saved to a memory.
For the PC/USB memory requirements to use this function, see "Peripheral Equipment
Specifications (CB14A005)".
Selecting a sampling period, the sampling targets and applicable operation rules, and executing
a sampling displays a graph and a list.
Specify the sampling target by area. Sub areas and management points included in the area will
become targets.
There are two modes for displaying the sampling results: area sampling and management point
sampling.
In area sampling mode, results are sampled by area and only sub areas included in the selected
area are displayed.
In the management point sampling mode, the management points (including management points
of sub areas) included in the selected area are displayed.
The sampled information is presented in two tabs: Failure to turn off tab where management
points that were operating when they should be stopped are sampled, and Setpoint gap tab
where indoor units with gaps between the actual setpoint and the setpoint that should be set are
sampled.
NOTE
Failure to turn off and setpoint gap times are sampled per period.
* 1 period ... 15 minutes obtained by dividing 1 hour by 4.
Example:
• Failure to turn off time
The equipment has been in operation the whole period though according to the
operation rule, it should be stopped.
• Setpoint gap time
The equipment has been in operation the whole period and the energy gap between the
average setpoint (actual value) and setpoint (operation rule) is positive.
However, if the operation during the period is due to multiple operation modes, sampling
is not performed.
Touch the Equipment op. Mgmt. button on the Energy Navigator tab of the Menu List screen and
display the Equipment operation management screen. (see "4-5 Menu List Screen: Energy
Navigator Tab")
265
1 period
1 period
1 period
3:00
3:15
3:30
User's Manual EM11A015B
intelligent Touch Manager
1 period
3:45
4:00

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcm601a52Dcm601a53Dcm002a51Dcm008a51Dcm009a51

Table of Contents