When the operation mode of an indoor unit being controlled is changed to Fan or Dry
Subsequent start/stop is not performed and remains in the status when it was changed (Setback
Active or Setback Inactive).
NOTE
• When an indoor unit where setback is active is stopped using remote controller, the unit
stops but the setback control continues.
• If an indoor unit receives a start/stop order from the iTM unit or Schedule function (see "5-1
Setting up a Schedule") while setback is active, the setback is canceled.
• The setback control will continue even if an indoor unit is stopped by the Timer Extension
function when setback is active.
The following describes how to set this up.
1. Touch the Temp. Setback button on the Automatic Ctrl. tab of the Menu List screen and display
the Setback Setup screen (see "4-5 Menu List screen: Automatic Ctrl. Tab").
2. Set up the relative setpoints for Setback High in (1).
Select the relative setup setpoint in the Relative Setup Setpoint combo box (2).
Select the relative setback setpoint in the Relative Setback Setpoint combo box (3).
The range of values you can select from is 1 to 7°C in increments of 1°C for both setup and
setback.
3. Set up the relative setpoints for Setback Low in (4).
Proceed in the same way as in step 2. However, you will not be able to set relative setpoints for
Setback Low exceeding those of Setback High.
153
(1)
(2)
(3)
(5)
User's Manual EM11A015B
intelligent Touch Manager
(4)