3 User safety instructions

2.1
Instructions for equipment using
R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
The appliance shall be stored as follows:
▪ in such a way as to prevent mechanical damage.
▪ in a well-ventilated room without continuously operating
ignition sources (example: open flames, an operating
gas appliance or an operating electric heater).
▪ in a room with dimensions as specified in
requirements for R32
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation (for example national gas regulation) and are
executed ONLY by authorised persons.

For the user

3
User safety instructions
Always observe the following safety instructions and regulations.
3.1

General

WARNING
If you are NOT sure how to operate the
unit, contact your installer.
WARNING
This appliance can be used by children
aged from 8 years and above and
persons with reduced physical, sensory
or mental capabilities or lack of
experience and knowledge if they have
been given supervision or instruction
Installation and operation manual
8
"13  Special
units" [ 4  19].
WARNING
▪ Take precautions to avoid excessive vibration or
pulsation to refrigeration piping.
▪ Protect the protection devices, piping and fittings as
much as possible against adverse environmental
effects.
▪ In case of direct connection to the outdoor unit,
ALWAYS support the piping at distances of 1  m and
2 m from the indoor unit and/or SV unit.
▪ Provide space for expansion and contraction of long
runs of piping.
▪ Design and install piping in refrigerating systems such
as to minimise the likelihood of hydraulic shock
damaging the system.
▪ Mount the indoor equipment and pipes securely and
protect them to avoid accidental rupture of equipment
or pipes in case of events such as moving furniture or
reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for
or detection of refrigerant leaks.
NOTICE
▪ Do NOT re-use joints and copper gaskets which have
been used already.
▪ Joints made in the installation between parts of the
refrigerant system shall be accessible for maintenance
purposes.
See
"To determine the charge
meets the requirement for charge limitation.
concerning use of the appliance in a
safe way and understand the hazards
involved.
Children SHALL NOT play with the
appliance.
Cleaning and user maintenance
SHALL NOT be made by children
without supervision.
WARNING
To prevent electrical shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet
hands.
▪ Do NOT place any objects containing
water on the unit.
limit"  [ 4   24] to check if your system
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1B – 2024.02