Operating Range; Overall Checking; Phase Protector (Optional) - Daikin FDM20JEVLK Installation Manual

Table of Contents

Advertisement

COOLING
Outdoor
DB (°C)
54
52
19
14
Ensure the following, in particular:-
1) The unit is mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.
Drainage check:- Pour some water into left side of drain pan
(drainage are in right side of unit).
• Test run:
1) Conduct a test run after water drainage test and gas leakage
test.
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is tted
to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase sequencer
operates, and the unit will not start. This device is located in the control box of the outdoor unit.
The following table shows the LED indicator light for phase protector under normal operation and fault conditions.
LED
PW
Description
(Red)
Normal operation
Reverse phase
T phase missing
S phase missing
R phase missing
S &T phase missing
+
+
Overload
+
Sensor missing
ON
NOTE
1. "+" indicates additional functions for PP01 phase protector.
2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 and relay 81 will cut off.

OPERATING RANGE

19
23
Indoor WB (°C)

OVERALL CHECKING

PHASE PROTECTOR (OPTIONAL)

P_R
P_S
P_T
(Yellow)
(Yellow)
(Yellow)
OFF
1-22
HEATING
Outdoor
WB (°C)
18
10
-9
15
DB = Dry Bulb
2) Watch out for the following:-
a) Is the electric plug rmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there smooth drainage of water?
• Check that:
1) Condenser fan is running, with warm air blowing off the
condensing unit.
2) Evaporator blower is running and discharge cool air.
3) The remote controller incorporates a 3 minute delay in the
circuit. Thus, it requires about 3 minutes before the outdoor
condensing unit can start up.
Actions
Switch off the unit. Check the 3 phase wiring.
Switch off the unit. Check the 3 phase wiring.
Switch off the unit. Check the 3 phase wiring.
Switch off the unit. Check the 3 phase wiring.
Switch off the unit. Check the 3 phase wiring.
High discharge temperature. Check the refrigerant system.
Switch off the unit. Plug in sensor.
Fast Blink
20
27
Indoor DB (°C)
WB = Wet Bulb
-