Daikin DCM601A51 User Manual page 121

Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

Fig. 2
Top
All
Indoor
Ventilator
Building A
1F North
1F South
4. The area created in step 3 (for example, Lavatory) is added to the area selected in step 2 (for
example, 1F North) as a member (Fig. 2).
NOTE
A newly created area is created under existing management points and areas.
You will not be able to create new areas in the following cases.
• The number of areas exceeds 650.
• The area selected in the Area List is a 10th hierarchical level area.
• The management points and areas included in the selected area total 650.
• The selected area is All or an area immediately under All.
• The name is the same as that of another area. (However, the name may overlap with that
of an Indoor, Ventilator, Dio, Analog, MultiState, Pulse, Outdoor, or Chiller unit predefined
in the All area.)
Aisle
Lighting A
Lavatory
Created after existing
members.
Meeting Room
Room A
Room B
Office
User's Manual EM11A015B
intelligent Touch Manager
<Area Setup screen>
120