SMA PPM-10 Installation Manual page 65

Power plant manager
Hide thumbs Also See for PPM-10:
Table of Contents

Advertisement

SMA Solar Technology AG
Multifunctional switching inputs and switching outputs
Connectable switches
Type of connection
Conductor cross-section
Voltage measurement inputs
Maximum number of voltage measurement inputs
Compatible power analyzers
Type of the voltage measurement inputs
Measurement range of the voltage measurement be-
tween line conductor and neutral conductor
Measurement range of the voltage measurement be-
tween line conductor and line conductor
Impedance of the voltage measurement
* The maximum number of voltage measurement inputs depends on the variant ordered (Hybrid Controller XL 1xGMP /
Hybrid Controller XL 2xGMP / Hybrid Controller XL Synch)
Current measurement inputs
Maximum number of current measurement inputs
Compatible power analyzers
Type of the current measurement inputs
Current measurement range
Power consumption of the current measurement internal
resistor
Minimum nominal output power of the current transform-
ers
Type of connection
Conductor cross-section
Maximum cable length
Overvoltage category as per IEC 60664-1
* The maximum number of current measurement inputs depends on the variant ordered (Hybrid Controller XL 1xGMP /
Hybrid Controller XL 2xGMP / Hybrid Controller XL Synch)
Tolerances of the measuring modules of simple current and voltage measurement and synchronization
Voltage measurement (reference value: nominal voltage
of the measuring module)
Current measurement (reference value: nominal current
of the measuring module)
Installation Manual
Potential-free switches
Spring-cage terminal
1.5 mm² to 2.5 mm²
Hybrid Controller L
3
Yes (in acc. with IEC 60664-1)
Three-phase
100 V to 277 V
170 V to 480 V
> 2 MΩ per line conductor
Hybrid Controller L
6
Janitza UMG 604, SMA FSC-11-DAQ
Three-phase
0 A to 1 A
< 100 mVA
Spring-cage terminal
1.5 mm² to 2.5 mm²
-0.1% to +0.1%
-0.3% to +0.3%
10 Technical Data
Hybrid Controller XL
1 to 3*
Hybrid Controller XL
1 or 2*
2.5 VA
100 m
III
PPM-10-IA-en-16
65

Advertisement

Table of Contents
loading

Table of Contents