SMA SUNNY TRIPOWER 60 Technical Information

SMA SUNNY TRIPOWER 60 Technical Information

Hide thumbs Also See for SUNNY TRIPOWER 60:
Table of Contents

Advertisement

Technical Information

SUNNY TRIPOWER 60 /

SUNNY HIGHPOWER PEAK1
Description of the Operating Parameters
ENGLISH
F1
F1
F2
F2
F3
F3
F4
F4
Ho me
Ho me
Ba ck
Ba ck
O K
O K
STP60-SHP75-10-Parameter-TI-en-12 | Version 1.2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SUNNY TRIPOWER 60 and is the answer not in the manual?

Questions and answers

Summary of Contents for SMA SUNNY TRIPOWER 60

  • Page 1: Technical Information

    Technical Information SUNNY TRIPOWER 60 / SUNNY HIGHPOWER PEAK1 Description of the Operating Parameters Ho me Ho me Ba ck Ba ck ENGLISH STP60-SHP75-10-Parameter-TI-en-12 | Version 1.2...
  • Page 2: Table Of Contents

    Table of Contents SMA Solar Technology AG Table of Contents Information on this Document..................... Grid Protection Settings ....................... Nominal Voltage ............................. Nominal Frequency............................Voltage-Dependant Disconnection ......................... 2.3.1 Disconnection due to Undervoltage ....................... 2.3.2 10-Minute Average Value..........................2.3.3 Disconnection due to Overvoltage .........................
  • Page 3 Table of Contents SMA Solar Technology AG 5.3.6 PF(U) - Power Factor as a Function of Grid Voltage..................18 5.3.7 PF(ext) - Power Factor as a Function of an External Setpoint................ 18 5.3.8 P(V) – Active Power as a Function of Grid Voltage..................19 5.3.9...
  • Page 4: Information On This Document

    1 Information on this Document SMA Solar Technology AG 1 Information on this Document This document is valid for: • STP 60-10 (Sunny Tripower 60) from software version 1.80 • STP 60-JP-10 (Sunny Tripower 60) from software version 1.80 • SHP 75-10 (Sunny Highpower Peak1) from software version 1.90 •...
  • Page 5: 10-Minute Average Value

    2 Grid Protection Settings SMA Solar Technology AG 2.3.2 10-Minute Average Value The ten-minute average value is defined in the standard EN 50160 as maximum threshold for a continuous high voltage in the grid. If this value is exceeded, the inverter is disconnected from the utility grid.
  • Page 6: Frequency-Dependent Disconnection

    2 Grid Protection Settings SMA Solar Technology AG Parameter name Setting option MAN_RST_UN_VTG on (1), off (0) MAN_RST_OV_FREQ on (1), off (0) MAN_RST_UN_FREQ on (1), off (0) MAN_RST_PID on (1), off (0) MAN_RST_AID on (1), off (0) Frequency-Dependent Disconnection 2.5.1...
  • Page 7: Reconnection Time

    3 Grid Failure SMA Solar Technology AG 2.6.2 Reconnection Time If a fault on the grid makes the inverter disconnect and the grid then afterwards stabilizes within the allowed voltage and frequency ranges, then the inverter is allowed to reconnect to the grid with this time delay. The reconnection time is usually shorter than the connection time, but it can also be the same time or longer than the connection time.
  • Page 8: Phase Failure Detection

    3 Grid Failure SMA Solar Technology AG Phase Failure Detection The phase failure detection is used to determine the failure of one or more line conductors of the utility grid. In case of a grid failure, the grid relays open.
  • Page 9: Settings Of Grid Management Services: Fault Ride-Through (Frt)

    4 Settings of Grid Management Services: Fault Ride-Through (FRT) SMA Solar Technology AG 4 Settings of Grid Management Services: Fault Ride-Through (FRT) The inverter is equipped with the Fault Ride-Through function for both undervoltage (LVRT) and overvoltage (HVRT/ OVRT) situations. Although the FRT function belongs to grid management services, it is stored in the inverter. The FRT function is set to cope with voltage dips down to 0% UNOM without time limit.
  • Page 10 4 Settings of Grid Management Services: Fault Ride-Through (FRT) SMA Solar Technology AG For reactive power feed-in, the positive and negative sequence components are considered separately. The half-cycle root-mean-square values of the positive and negative sequence components of the grid voltage during the grid fault are compared with the average root-mean-square values before the fault.
  • Page 11 4 Settings of Grid Management Services: Fault Ride-Through (FRT) SMA Solar Technology AG Figure 4: FRT_IQ_MODE = 1: as per SDLWind (IEC 62850-90-7) In both operating modes, there is a common set of parameters which have to be set for the FRT functionality to work properly: 1.
  • Page 12: Settings Of Grid Management Services

    0% to 100% 5 Settings of Grid Management Services The following parameters for grid management services are loaded to the SMA Inverter Manager (IM) and only used here. The settings are divided into groups. The groups reflect the various grid management services (control modes).
  • Page 13: Default Settings

    Start/Stop control Setpoint for P, Q, PF Parameters for control modes Figure 5: Overview of a system with inverters, SMA Inverter Manager, local load, power meter and definition of Point of Common Coupling (PCC). Default Settings 5.1.1 Selecting the Control Modes for Reactive Power Provision Reactive power references can either be given as a direct reference for reactive power (Q) or as an indirect reference via the power factor (PF).
  • Page 14: Night Mode

    5 Settings of Grid Management Services SMA Solar Technology AG 5.1.2 Night Mode The system with an inverter provides reactive power also in night mode. Therefore, the inverters are not switched off after sunset. Information: If no primary energy source is available, only the control modes 1 to 5 can be used for reactive power provision.
  • Page 15: Nominal Voltage

    5 Settings of Grid Management Services SMA Solar Technology AG 5.1.6 Nominal Voltage This parameter refers to the nominal grid voltage at the point of common coupling. The parameter is used to scale the grid voltage for the control modes where the grid voltage is the independent variable, i.e. for Q(U), PF(U) and P(U). If no external energy meter is used, this parameter should have the same value as UNOM in the protection part of the grid code file.
  • Page 16: Active Power Ramp Rates

    5 Settings of Grid Management Services SMA Solar Technology AG 5.2.5 Active Power Ramp Rates The active power is ramped according to these setting whenever the external setpoint for active power is changed. Note that two parameters are available: one for decreasing and one for increasing setpoints.
  • Page 17: Control Modes

    5 Settings of Grid Management Services SMA Solar Technology AG Control Modes The general approach for the control modes is based on the structure in the technical report of the standard IEC 61850-90-7 (see the figure below). Up to five parameters are used to program the local modes depicted above. The parameter RmpTmsPT1 is the rise time from 0% to 95% (equal to 3τ) for the low-pass filter applied on the independent variable (e.g.
  • Page 18: Q(S) - Reactive Power As A Function Of Apparent Power

    5 Settings of Grid Management Services SMA Solar Technology AG Parameter name Setting range Step size Q_of_P P: Active power (independent values) from -100% to 100% of nomi- nal power Q: Reactive power (dependent values) from -100% to 100% of nomi- nal power 5.3.3...
  • Page 19: P(V) – Active Power As A Function Of Grid Voltage

    5 Settings of Grid Management Services SMA Solar Technology AG 5.3.8 P(V) – Active Power as a Function of Grid Voltage This control mode uses the grid voltage to generate a threshold for the active power so that the grid voltage can be controlled at the point of common coupling.
  • Page 20 5 Settings of Grid Management Services SMA Solar Technology AG Figure 6: Parameterization of frequency control Position Explanation Typical programming of the FP_of_f characteristic curve when hysteresis is not required, e.g. as per VDE AR-N 4105. Thus, the two characteristic curves in the reference table contain equal co-or- dinates (x, y).
  • Page 22 www.SMA-Solar.com...

Table of Contents