6 Electrical Connection
Destruction of the measuring module due to short circuit
If a voltage-measurement device is connected to a measuring module in a 4-conductor utility grid, and a voltage
converter is not interconnected, there must not be a conductive connection between the neutral conductor and
grounding conductor. A conductive connection between the neutral conductor and the grounding conductor may
occur by inserting a jumper and then can result in a short circuit during commissioning. The measuring module is
destroyed when a short circuit occurs.
• If a voltage-measurement device without a voltage converter is connected to measuring module 1 in the 4-
conductor utility grid, ensure that the jumper between the terminals X200:4 and X200:5 has been removed.
• If a voltage-measurement device without a voltage converter is connected to measuring module 2 in the 4-
conductor utility grid, ensure that the jumper between the terminals X200:9 and X200:10 has been removed.
• If a voltage-measurement device without a voltage converter is connected to measuring module 3 in the 4-
conductor utility grid, ensure that the jumper between the terminals X200:14 and X200:15 has been
removed.
Terminal assignment:
Measuring
Voltage mea-
module
surement
K103
1
K104
2
K105
3
Requirements:
☐ The connected local utility grid must be a 4-conductor or a 3-conductor utility grid according to its grid type. If
another grid type is used, the connection of the current transformers must be coordinated with SMA Solar
Technology AG.
44
PPM-10-IA-en-16
NOTICE
Available with option
Hybrid Controller L
Hybrid Controller XL 1xGMP
Hybrid Controller XL 2xGMP
Hybrid Controller XL Synch
Hybrid Controller L
Hybrid Controller XL 2xGMP
Hybrid Controller XL Synch
Hybrid Controller L
Hybrid Controller XL Synch
SMA Solar Technology AG
Conductor
Line conductor L1
Line conductor L2
Line conductor L3
Neutral conductor N
Grounding conductor
PE
Line conductor L1
Line conductor L2
Line conductor L3
Neutral conductor N
Grounding conductor
PE
Line conductor L1
Line conductor L2
Line conductor L3
Neutral conductor N
Grounding conductor
PE
Terminal on product
X200:1
X200:2
X200:3
X200:4
X200:5
X200:6
X200:7
X200:8
X200:9
X200:10
X200:11
X200:12
X200:13
X200:14
X200:15
Installation Manual

Advertisement

Table of Contents
loading

Table of Contents