SMA PPM-10 Installation Manual page 47

Power plant manager
Hide thumbs Also See for PPM-10:
Table of Contents

Advertisement

SMA Solar Technology AG
Damage to optical fibers due to too tight bend radii
Excessive bending or kinking will drop below of the permissible bend radii. When dropping below the permissible
bend radii, the optical fibers may be damaged.
• Observe the minimum permissible bend radii of the optical fibers.
Procedure:
1. Loosen the cable gland of the module.
2. Insert the optical fibers through the cable gland into the module.
3. Strip sufficient insulation off the optical fibers.
4. Install the optical fibers:
• If optical fiber pigtails are used, splice the optical fibers with the optical fiber pigtails and secure the splice
points in the splice holders.
• If subscriber connectors are used, install the subscriber connectors on the optical fibers.
• Push the plug down until it locks in the adapters.
5. Position the fiber in the fiber holder. Observe the bend radii of the optical fibers.
6. Tighten the cable gland.
Installing the network cables
Requirements:
☐ The network cables must be inserted into the product.
Procedure:
1. Take the RJ45 Keystone jacks out of the accessory kit.
2. Connect the network cables to the RJ45 Keystone jacks:
• Dismantle the network cable by 30 mm.
• Fold the braided shielding.
• Remove the foil shield from the insulated conductor pairs.
• With the adhesive side facing the inside, attach the aluminum foil from the outside so that it is flush with the
braided shielding.
• Lead the network cable through the cable organizer.
• Insert the conductors into the slots of the cable organizer. Use the appropriate color coding according to the
standard of your choice.
Insulated conductor
pair
1
Installation Manual
NOTICE
Insulated conductor
color
white/blue
blue
Contact-568A
5
4
6 Electrical Connection
Contact-568B
5
4
PPM-10-IA-en-16