Lenovo ThinkSystem SR950 Setup Manual page 321

Hide thumbs Also See for ThinkSystem SR950:
Table of Contents

Advertisement

Figure 84. Lower fan cage removal
Step 1.
Press the button on each compute tray release lever; then, rotate the release levers until they are
perpendicular to the tray.
Step 2.
Press the fan cage releases at either side of the fan cage; then, pull the fan cage toward the front of
the compute tray and lift the cage slightly to access the connector on the underside of the fan cage.
Step 3.
Disconnect the cable from the connector
Attention: To prevent damage to components, lift the fan cage straight up when removing it from
the tray.
Step 4.
Lift and remove the fan cage from the tray.
If you are instructed to return the fan cage, follow all packaging instructions, and use any packaging
materials for shipping that are supplied to you.
Install a fan cage (upper tray)
The upper fan cage is in the upper compute tray or optional storage tray that is accessed from the front of
the server. Fan cages are keyed and each can be used only in one type of tray (upper or lower). Numbers on
the fan cages are right-side up when the compute or storage tray is installed in the chassis. Install the upper
fan cage by connecting the fan cage electrical connector, inserting the fan cage in the upper tray, and
pushing it backward until it locks in place.
S002
in the underside of the fan cage.
1
Appendix B. Component reference
317

Advertisement

Table of Contents
loading

Table of Contents