400V class, FR-F842 (when input power supply is 440V)
(For the applicable cables of the converter unit (FR-CC2) refer to the FR-CC2 Instruction Manual.)
Applicable
Terminal screw
inverter type
4
size *
FR-F842-
07700(355K)
M12 (M10)
08660(400K)
M12 (M10)
09620(450K)
M12 (M10)
10940(500K)
M12 (M10)
12120(560K)
M12 (M10)
*1
For the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower, the recommended cable size is that of the HIV cable (600V
class 2 vinyl-insulated cable) with continuous maximum permissible temperature of 75°C. Assumes that the surrounding air
temperature is 50°C or less and the wiring distance is 20m or less.
For the FR-F820-03160(75K) or higher, the FR-F840-01800(75K) or higher, and the FR-F842 models, the recommended cable size is
that of the LMFC cable (heat resistant flexible cross-linked polyethylene insulated cable) with continuous maximum permissible
temperature of 90°C. Assumes that the surrounding air temperature is 50°C or less (40°C or less for the FR-F842 models) and wiring
is performed in an enclosure.
*2
For all the 200V class capacities and FR-F840-00930(45K) or lower, the recommended cable size is that of the THHW cable with
continuous maximum permissible temperature of 75°C. Assumes that the surrounding air temperature is 40°C or less and the wiring
distance is 20m or less.
For the FR-F840-01160(55K) or higher, and the FR-F842 models, the recommended cable size is that of THHN cable with continuous
maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 40°C or less and wiring is performed in
an enclosure.
(Selection example for use mainly in the United States.)
*3
For the FR-F820-00770(18.5K) or lower and FR-F840-00930(45K) or lower, the recommended cable size is that of the PVC cable with
continuous maximum permissible temperature of 70°C. Assumes that the surrounding air temperature is 40°C or less and the wiring
distance is 20m or less.
For the FR-F820-00930(22K) or higher, the FR-F840-01160(55K) or higher, and the FR-F842 models, the recommended cable size is
that of XLPE cable with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 40°C
or less and wiring is performed in an enclosure. (Selection example for use mainly in Europe.)
*4
FR-F820/F840: The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, P/+, N/–, P1, P3, and a screw for
earthing.
The screw size for earthing of FR-F820-00930(22K) or higher and FR-F840-04320(185K) or higher is indicated in brackets.
The screw size for P/+ terminal for connecting an option to FR-F840-03250(132K) or FR-F840-03610(160K) is indicated in brackets.
FR-F842: The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, P/+, N/–, and a screw for earthing.
The screw size for earthing is indicated in brackets.
Crimping
terminal
Tightening
torque [Nm]
U, V, W
46
200-12
46
C2-200
46
C2-250
46
C2-250
46
C2-200
Cable sizes
1
HIV, etc. [mm²] *
Earth
U, V, W
P/+, N/–
cable
gauge
2×200
2×150
100
2×200
2×200
100
2×250
2×200
100
2×250
2×250
2×100
3×200
3×200
2×100
WIRING
AWG/
PVC, etc. [mm²] *
2
MCM *
Earth
U, V, W
U, V, W
cable
gauge
2×350
2×185
2×95
2×400
2×185
2×95
2×500
2×240
2×120
2×500
2×240
2×120
3×350
3×185
2×150
3
15