Maintenance Only To Be Performed By A Qualified Service Technician - NTI FTVN085 Installation Start-Up Maintenance

Residential condensing gas boiler
Hide thumbs Also See for FTVN085:
Table of Contents

Advertisement

3. If applicable, check the condensate neutralizer and ensure it is full
of condensate neutralizing marble chips.
C. Maintenance Only to be Performed by a Qualified Service
Technician
Removing the Cabinet Cover and Inspecting the Boiler
Before carrying out any work on the boiler, switch off the power supply
at the external power switch and circuit breaker. Close the external
gas shutoff.
DANGER
Ensure power and gas to the appliance are shut off before
performing the following operations. Failure to do so will
result in substantial property damage, severe personal
injury, or death.
See Figure 84 to access the interior of the boiler:
1.
Release the four (4) latches from the front cover (two [2] each
side). Lift and remove the front cover from the cabinet (a).
2.
Remove the screw securing the control panel to the cross-member
(b).
3.
Push in the tabs and pull the control panel housing forward (c).
(a)
(b)
(c)
Figure 84 - Removing the Cover and Control Panel Housing
Check Water and Gas Piping
1. Remove the boiler cover and perform a gas leak inspection following
Operating Instructions on page 2 of this manual. If gas odor or leak
is detected, follow procedures on page 2. Call a qualified service
technician.
2. Visually inspect for leaks around the boiler water connections
and around the heat exchanger. Visually inspect the external
system piping, circulators, and system components and fittings.
Immediately call a qualified service technician to repair any leaks.
WARNING
Have leaks fixed at once by a qualified service technician.
Failure to comply could result in substantial property
damage, severe personal injury, or death.
Before Starting Maintenance:
1. Ensure the power and gas remain off.
2. Close the valves of heating and hot water circuit.
3. Remove the front panel as shown in Figure 84.
4. If necessary, empty the appliance on the water side.
Draining Procedure
To drain the heating system:
1. Ensure the boiler power and gas remain off.
2. Open the manual purge valve.
3. Open the system drain valve and collect the escaping water in a
container.
4. Drain the water from the lowest points of the system (where
applicable).
If the system is to be inactive in areas where the room temperature
may fall below 0°C during winter, it is recommended that anti-freeze
liquid be added to the heating system in order to avoid the need for
repeated draining. Ensure the antifreeze used is compatible with the
stainless steel boiler heat exchanger.
WARNING
NEVER use any toxic chemical, including automotive,
standard glycol antifreeze, or ethylene glycol made for
hydronic (non-potable) systems. These chemicals can
attack gaskets and seals in water systems, are poisonous if
consumed, and can cause personal injury or death.
It is recommended to use antifreeze which contains PROPYLENE
GLYCOLS as these inhibit corrosion. Use the quantities and formulation
suggested by the antifreeze manufacturer to protect against freezing
in your region and prevent scaling and corrosion.
Regularly check the pH level of the water/anti-freeze mix in the boiler
circuit and replace it when the value measured is lower than the limit
prescribed by the manufacturer.
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE.
The manufacturer will not be held liable for any damage caused by
the appliance or the system due to the use of inappropriate antifreeze
substances or additives.
Draining the DHW System and Indirect Water Heater
Every time there is a danger of freezing, the domestic hot water system
must be drained as follows:
1. Shut off the main water inlet valve.
2. Open all the hot and cold water taps.
3. Drain the water from the lowest points of the system.
Part 14 - Maintenance
89

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ftvn110Ftvn150Ftvn199Ftvn110cFtvn150cFtvn199c ... Show all

Table of Contents