Part 13 - Troubleshooting; Boiler Protection Devices; Blocking Error; Lockout Error - NTI FTVN085 Installation Start-Up Maintenance

Residential condensing gas boiler
Hide thumbs Also See for FTVN085:
Table of Contents

Advertisement

A. Boiler Protection Devices
The boiler is protected from malfunctioning by means of internal
checks performed by the electronic microprocessor PCB, which stops
the boiler from operating if necessary. In the event of the boiler being
shut off in this manner, a code appears on the display which refers to
the type of shut-off and the reason behind it.
There are two types of shut-off:

1. Blocking Error

A blocking error means the boiler will restart
automatically as soon as the problem which
caused the error clears or is removed; the error
is indicated by the «
appears on the display followed by the error
code.
For example, if the boiler indicates a 110 error
code, the error will clear automatically when
the CH temperature decreases. The boiler will
restart and operate normally.
NOTE: Contact a qualified service technician if
the error continues to occur.
In the event of Error 108 - Shut-off due
to insufficient water pressure inside the
heating circuit - Pressure can be increased
by filling the heating circuit. See filling and
purging procedures, this manual.
If Error 108 occurs frequently and system needs repeated refilling, turn
the boiler off. Turn the external electric power to the OFF position. Shut
off the main gas valve. Contact a qualified service technician to check
for any leaks of water.

2. Lockout Error

A lockout error means the boiler does not return to operation after the
error condition goes away. The
control panel to restore boiler operation.
If the error condition occurs often contact a qualified service technician.
Figure 83 - Lockout Error Example
WARNING
Important
Contact a qualified service technician for assistance if a
Lockout Error occurs frequently. For safety reasons, the
boiler will permit a maximum of five (5) resets in 15 minutes
(five [5] presses of the RESET button). A sixth (6th) attempt
within this 15 minute period will lock out the boiler. The boiler
will only operate again after the electrical supply has been
disconnected and reconnected.
Repeated Lockout Error conditions could indicate a serious
error with the boiler or installation. Failure to contact a
qualified service technician to troubleshoot the error could
result in substantial property damage, serious personal
injury, or death.
» symbol which
Figure 81 - Blocking
Error Example
Figure 82 - Shut-Off
Error for Low Water
Pressure
button must be pressed on the

3. Malfunction Warning

This warning is shown by the display in the following format:
5 P1 = FIRST IGNITION ATTEMPT UNSUCCESSFUL
The first part of the error code (e.g. 1 01) indicates the affected
operational assembly.
1 - Primary Circuit
2 - Domestic Hot Water Circuit
3 - Internal Electronic Part
4 - External Electronic Part
5 - Ignition and Detection
6 - Air inlet - flue gas outlet
7 - Multi-zone Heating