NTI Trinity Ti 150 Installation And Operation Instruction Manual

NTI Trinity Ti 150 Installation And Operation Instruction Manual

Hide thumbs Also See for Trinity Ti 150:

Advertisement

Trinity T
1.0 SPECIFICATIONS................................................................................................. 2
2.0 INSTALLATION REQUIREMENTS .................................................................. 3
2.10 LOCATION ....................................................................................................... 3
3.0 VENTING................................................................................................................ 4
3.1 VENT PIPE MATERIAL .................................................................................... 4
3.2 VENTING CLEARANCES................................................................................. 4
3.3 VENTING CONFIGURATIONS ........................................................................ 5
3.4 DETERMINING VENT LENGTHS ................................................................... 8
4.0 CONDENSATE DRAIN......................................................................................... 9
5.0 INSTALLING GAS PIPING ............................................................................... 10
.................................................................................................... 10
6.0 HEATING SYSTEM PIPING ............................................................................. 11
6.1 PRIMARY LOOP PLUMBING ........................................................................ 12
6.2 SECONDARY LOOP HEATING SYSTEM..................................................... 15
6.2.1 Multiple Zones using Zone Valves.............................................................. 15
6.2.2 Multiple Zones using Pumps ...................................................................... 15
6.2.3 Multiple Zones with different temperatures................................................ 16
6.3 DOMESTIC COMBI SYSTEM ((( OPTIONAL)))........................................... 17
7.0 WIRING ................................................................................................................ 19
7.2.1 Multiple 4 wire Zone Valves....................................................................... 21
7.2.2 Multiple Zones with Taco Valve controller ................................................ 22
7.2.3 Multiple Zones Pump controller................................................................. 23
7.2.4 Multiple Temperature Zones with Injection Pumps.................................... 24
8.0 SENTRY 2100T CONTROLLER ....................................................................... 25
9.0 LIGHTING BOILER ........................................................................................... 28
9.1 INITIAL START-UP ......................................................................................... 28
9.2 RE-LIGHTING UNIT........................................................................................ 28
9.3 TURN OFF BOILER ......................................................................................... 28
10.0 TROUBLE SHOOTING .................................................................................... 29
11.0 SEQUENCE OF OPERATION ......................................................................... 32
13.0 ANNUAL MAINTENANCE AND INSPECTION........................................... 34
14.0 PARTS LIST ....................................................................................................... 35
15.0 WARRANTY ...................................................................................................... 36
................................................................................. 2
...................................................................................... 10
..................................................................... 20
............................................................................ 21
................................................................. 34
VERSION DATE: 12-01-05
Installation and
i
Operation Instructions
Trinity Ti Boiler Only

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Trinity Ti 150 and is the answer not in the manual?

Questions and answers

Summary of Contents for NTI Trinity Ti 150

  • Page 1: Table Of Contents

    Trinity Ti Boiler Only Trinity T VERSION DATE: 12-01-05 Installation and Operation Instructions 1.0 SPECIFICATIONS....................2 1.1 H ................. 2 LTITUDE PERATION 2.0 INSTALLATION REQUIREMENTS ..............3 2.10 LOCATION ....................... 3 3.0 VENTING........................ 4 3.1 VENT PIPE MATERIAL ..................4 3.2 VENTING CLEARANCES.................
  • Page 2: Specifications

    CAUTION: Warning 1. IT IS THE RESPONSIBILITY OF THE THIS BOILER MUST HAVE WATER HOMEOWNER TO KEEP THE VENT FLOWING THROUGH IT WHENEVER TERMINAL CLEAR OF SNOW AND ICE. THE BURNER IS ON. FAILURE TO DO CERTIFIED CARBON MONIXIDE THIS WILL DAMAGE THE UNIT AND VOID THE WARRANTY.
  • Page 3: Installation Requirements

    2.0 INSTALLATION REQUIREMENTS The installation of your NY Thermal Trinity gas boiler must conform to the requirements of your local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where required by the Authority, the installation must conform to the standard for “Controls and Safety Devices for Automatically Fired Boilers ANSI/ASME CSD-1.
  • Page 4: Venting

    ANY WEIGHT OR LATERAL FORCE detailed in this section. Under no conditions, TO THE FLUE BOX. NTI does not may this unit vent gases into a masonry warranty damages to the flue box. chimney, unless it is vacant, and utilizes the sch.
  • Page 5: Venting Configurations

    • Underneath a wooden verandah, porch, or deck. • Underneath cement verandah, porch, or deck, unless both ends are open and the exhaust pipe is installed at least 24” under the deck floor. • So situated that the flue gases are directed towards brickwork, siding, or other construction, in such a manner that may cause damage from heat or condensate from the flue gases •...
  • Page 6 Concentric vent terminal Clearances and requirements of this manual Use NTI part # 82666 or supersede, those of the Instructions enclosed in York Part# 1CT0303 vent terminal #650.75-N2, which contain more detailed assembly instructions. Apply plate here Gas Vent Directly Below...
  • Page 7 MUST be secured to the side of the building above grade, as shown, to provide rigidity. NTI Provides a mounting bracket PN. 82075 for securing the exhaust pipes. Ensure that the vent clearances are maintained (Inlet minimum 12”...
  • Page 8: Determining Vent Lengths

    10.) Install the vent screens provided into both the inlet and exhaust vent terminal elbows. The screen must be on the outside of the last elbow. Install the screen into the female opening of the elbow. Then cut a small piece of pipe to sandwich the screen into the elbow. NOTE be sure that the small piece of pipe cut, does not extend past the end of the elbow.
  • Page 9: Condensate Drain

    Vent piping outside the Building is permitted under the following conditions: 1. The maximum length outside the building is 20 feet. 2. Only 3” pipe can be used. 3. All normal termination clearances Supports every 24” are maintained. 4. All exterior exhaust vent pipes are insulated with 3.5”-ID, ½”-thick Closed Cell Foamed Polyolefin Exhaust...
  • Page 10: Installing Gas Piping

    5.0 INSTALLING GAS PIPING Gas cock 5.1 Installation shut Off Gas valve Valve to be Refer to the current National Fuel Gas "T" type Code ANSI Z223.1/NFPA 54 or handle Air Inlet CAN/CGA B149.1 installation codes, and local codes for gas piping requirements and sizing.
  • Page 11: Heating System Piping

    The Trinity boiler employs a pneumatic modulation system. This modulation system Manifold increases or decreases the velocity of the blower, to meet the demand for heating. The gas valve senses this change in blower Input Screw Gas IN pressure and introduces the required amount of gas to ensure correct combustion.
  • Page 12: Primary Loop Plumbing

    ALL the radiation or where local authorities require it. NTI recommends installing a LWCO or flow switch to prevent the boiler from firing without water in the heat exchanger.
  • Page 13 Plumbing Low Water cut off • Ensure that the water line of the “Low Water Cutoff” is at least 6” Break 120Volt above the top of the boiler. Air Vents power supply • It is recommended that the LWCO to Boiler. Relay must be be situated so that it can be tested Water Line...
  • Page 14 Primary Loop For Heating Model Legend Quantity and location of shutoff valves, and drains, are at the discretion of the installed. A- Back flow preventor B- Fill valve (set at 12 psi) C- Diaphragm expansion tank D- Cast Iron Air scoop, for excessive air Ti150 1”...
  • Page 15: Secondary Loop Heating System

    6.2 SECONDARY LOOP HEATING SYSTEM The following are typical piping systems. It is the responsibility of the installing contractor to determine which system best meets the need of the installation. Contractor modifications to these instructions may be required, based upon existing piping and system design. 6.2.1 Multiple Zones using Zone Valves Max.
  • Page 16: Multiple Zones With Different Temperatures

    6.2.3 Multiple Zones with different temperatures Using pumps and tempering valves Max. 12” apart Primary Loop Tempering valve See figure 7.2.3 “Multiple Zones using pumps, and pump controller” Zone 1 Low Temp. By setting the tempering valves to different settings, multiple temperatures can be obtained.
  • Page 17: Domestic Combi System ((( Optional)))

    “Indirect Water Heater” is highly recommended. The Trinity Combi Note: Locations of plumbing connections are not be as shown, refer to labels on boiler, contact NTI incorporates all the with any questions. features of the Standard...
  • Page 18 To improve domestic hot water performance, Sentry versions T1.5 and newer, installed on Combi boilers, go into a “Storage Mode” when demands for both space and domestic heat are finished. The control will enter “Storage Mode” if the burner is on at the end of a demand. Once in “Storage Mode” the burner goes to low fire, the 3-way diverting valve is energized (position “A”), and the circulator is powered until a boiler temperature of 160°F is reached, at which point the control reverts to “Standby Mode”.
  • Page 19: Wiring

    Table 1: Ti150C Flow rates (flow rates in us gpm) Inlet Water Temperature (deg. F) Table 2: Ti200C Flow rates (flow rates in usgpm) Inlet Water Temperature (deg. F) To avoid having too much flow at your faucets use the shut off valve after the mixing valve to limit the overall flow of domestic hot water.
  • Page 20: Simplified Wiring Connections

    7.1 Simplified Wiring Connections Heat and Indirect Wiring Indirect 120V WIRING Aquastat Outdoor Probe Primary Pump CAUTION White Contacts that energize * Indirect Black these inputs Circulator MUST BE DRY CONTACTS ONLY 120/1/60 15 AMP FUSED Electrical Box POWER SUPPLY 5V WIRING Combi Wiring 120V WIRING...
  • Page 21: Advanced Wiring Systems

    7.2 Advanced Wiring Systems 7.2.1 Multiple 4 wire Zone Valves Legend P1- Primary Pump P3-Secondary pump P2- Indirect pump, or C B - T r i n i t y C o n t r o l b o x C o m b i V a l v e Burner On Heating Pump...
  • Page 22: Multiple Zones With Taco Valve Controller

    7.2.2 Multiple Zones with Taco Valve controller (Models ZVC403 to ZVC 406) Legend P1- Primary Pump P3-Secondary pump P2- Indirect pump, or C B - T r i n i t y C o n t r o l b o x C o m b i V a l v e Burner On Heating Pump...
  • Page 23: Multiple Zones Pump Controller

    7.2.3 Multiple Zones Pump controller (Models Taco SR504, Argo ARM 861 Series) Legend P1- Primary Pump P3-Secondary pump P2- Indirect pump, or C B - T r i n i t y C o n t r o l b o x C o m b i V a l v e Indirect thermostat,...
  • Page 24: Multiple Temperature Zones With Injection Pumps

    7.2.4 Multiple Temperature Zones with Injection Pumps (Models Taco SR504, Argo ARM 861 Series And Tekmar 356 controller ) Indirect thermostat, or combi flow switch Loop 1 (Hi Temp.) Thermostat, or manifold end switch Loop 2 (Lo Temp.) Thermostat, or manifold end switch Legend P1- Primary Pump...
  • Page 25: Sentry 2100T Controller

    Once the room thermostat is satisfied, it breaks power to the TT terminal of the pump controller, which opens the X –X contacts, which opens the T-C circuit. The Pumps and burner turn off. In an injection system, it is important to understand the effect of flow and temperature set points. It is recommended that the Sentry controller’s set point is at least 20°F higher than the desired Mix temperature of the Hottest Loop.
  • Page 26 Setting Sentry 2100T Operation The Trinity boiler employs a pneumatic modulation system. This modulation system increases or decreases the velocity of the blower, to meet the demand for heating. The gas valve, senses this change, in blower pressure, and introduces the required amount of gas, to ensure correct combustion. The term “Set Point” is used to indicate the desired temperature that the Trinity will try and maintain, by increasing or decreasing the input.
  • Page 27 Determining Reset Temperature HI Calc Once the control identifies the presence of a good outside sensor, the control will automatically reduce the HI setting, based upon the outdoor temperature. The calculated HI setpoint (HI ) is calculated as follows : Example: Hi=200, Calc RES=70 , Air Temperature=32 Note:...
  • Page 28: Lighting Boiler

    9.0 LIGHTING BOILER 9.1 INITIAL START-UP • Ensure that the boiler is wired in accordance with this manual. • Ensure that the gas shut-off valve is turned on, and that the gas system has been fully tested for leaks. • Ensure that the system is completely filled with water, and that ALL the air is purged out. 1.
  • Page 29: Trouble Shooting

    10.0 TROUBLE SHOOTING This section is intended to assist the service technician in detecting and correcting common errors. The Sentry 2100 is equipped with an internal diagnostic system that verifies control operation. The following series of error codes has been developed to aid in diagnosing control problems: Problem Detected Problem Solution...
  • Page 30 1 – If 24V exists here but not at B1, indicates faulty relay when burner inside Sentry, contact NTI, replace control. light is on Check for 24 Volts between terminal F1 on 2 – If 24V is not present check for 24V at transformer.
  • Page 31 Momentarily remove the intake vent from the boiler during ignition, if unit lights smoothly with intake vent disconnected reconnect and check for proper combustion if unit maintains smooth operation after ignition. (See Section 5.2) Calibrate for proper combustion. If problem persists contact NY Thermal. Slight vibration can Use flexible gas line to insolate the vibration noises between the gas valve and the cause noise in the...
  • Page 32: Sequence Of Operation

    11.0 Sequence of operation The following is the normal sequence of operation for the trinity boiler. Trinity Sequence of operation 120v Power Displays version Boiler in Applied t2.0 standby mode Indirect thermostat Thermostat, End switch or flow switch closes A-C or relay closes T-C Energizes Combi...
  • Page 33 Wiring Diagram Electrical S1 L1 L2 S2 W 120V TRANSFORMER Green Brown Black Black Blue bare SENTRY 2100 Blue AIR SWITCH bare Purple Green Green GND BLOCK Bare VALVE BLOWER Brown GROUND Blue Green White Black 12.0 INSTALLATION CHECKLIST Installation a) Connect all plumbing, and ensure that there are no system leaks.
  • Page 34: Annual Maintenance And Inspection

    4. Set Sentry Controller to desired settings. 5. Turn thermostat up, Ignition will occur. Operational Checklist Ensure that Carbon Dioxide Readings are within the acceptable ranges. Using an appropriate Oxygen or Carbon Dioxide analyzer, take a sample of the flue gas. The sample must fall within the acceptable Carbon Dioxide ranges, which is 8% - 9.5% for natural, and 9.0%-10.5% for propane.
  • Page 35: Parts List

    14.0 PARTS LIST Replacement parts are available from your stocking wholesaler. Homeowners must contact their local Installer or Wholesaler. Installers or Wholesalers may contact NY Thermal Inc. for assistance at 506- 432-1130. Notes: *Used for Combi version only. P.N. Description 82657 Premix burner, 135.8 Ti-150 Only 82658...
  • Page 36: Warranty

    3. If you cannot contact your contractor or service rep. contact us at (506) 432-1130 to the attention or the service department. NTI cannot provide technical assistance, unless you are a trained heating technician. 4. Please realize that we as the boiler manufacturer will replace or credit the parts under warranty credits are at our cost, so don't purchase replacement parts from suppliers with hopes of receiving 100% credit.

This manual is also suitable for:

Trinity ti 200

Table of Contents

Save PDF